EasyManuals Logo

Tektronix GeoProbe G10 Installation Guide

Tektronix GeoProbe G10
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #165 background imageLoading...
Page #165 background image
G10 Installation Guide 7.13.2 165
D
Rev. 005-140228
STORAGE ENCLOSURE BONDING AND GROUNDING REQUIREMENTS
This section provides guidelines for installing storage enclosures for compliance with NEBS
Bonding and Grounding requirements of GR-1089-CORE, Issue 6. These bonding and
grounding connections satisfy the Telcordia NEBS requirements for supplemental bonding and
grounding connections. If you are not installing the equipment in a NEBS environment, you
can choose to bypass these guidelines and rely on the safety earth ground connections to the
DC PDUs.
Use the following guidelines when grounding equipment:
Ground equipment to a Common Bonding Network.
Use only copper wire cables for grounding purposes.
Ensure the equipment’s battery return terminals are in the configuration of an isolated
DC Return (DC-I), which means the equipment is grounded at the battery source.
Install equipment in a secured or controlled area that restricts access to trained
personnel when installing equipment in network telecommunication facilities. The
equipment should not be accessible to untrained personnel or the general public
without proper authorization and supervision.
Tektronix Communications | For Licensed Users | Unauthorized Duplication and Distribution Prohibited

Table of Contents

Other manuals for Tektronix GeoProbe G10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tektronix GeoProbe G10 and is the answer not in the manual?

Tektronix GeoProbe G10 Specifications

General IconGeneral
BrandTektronix
ModelGeoProbe G10
CategoryAccessories
LanguageEnglish