EasyManua.ls Logo

Temptronic ThermoStream TP04300 Series - Page 213

Temptronic ThermoStream TP04300 Series
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
. . . . .
ROUTINE MAINTENANCE
RTD Sensor Calibration (DUT Mode)
TP04300 Series Interface & Applications Manual 5-33
To calibrate an RTD sensor:
External Sensor
Method
(RTD Sensor)
1980_518.jpg
Step Action
1 Run system for half an hour at Ambient to stabilize components at normal
operating temperatures.
2 Toggle Head into Up position so System is not supplying main air flow
controlled to a setpoint (other than "Trickle" air flow).
NOTE: 4300B Systems should have the “Head: Lock” on. The “Head: Lock”
can be toggled on/off in the Utilities Screen.
3 Unplug any external RTD sensor plug from the RTD socket on the rear panel I/
O, and plug the Calibrator output plug into the RTD rear panel socket, taking
care to observe plug pin polarity.
4 Press the Utilities Screen tab, then press the "Sensor Calibration" button to
display Calibration Main Screen, then press "RTD’ to display the Calibrate
RTD Screen.
5 Set Calibrator output to the desired Low Calibration point (-60.0 °C), then press
"Next" to display Calibrate Low Temperature (RTD) Screen. Allow graph plot
to stabilize at low temperature.
6 Set Calibrator output to desired high Calibration point (+200.0 °C), then press
"Next" to display Calibrate High Temperature (RTD) Screen. Allow graph
plot to stabilize at high temperature.
7 Press "Next" to display Calibration Done (RTD) Screen, then press "Done" to
return to Utilities Screen.
8 Unplug the Calibrator output plug from the rear RTD socket, and replug the
external RTD sensor into the rear I/O socket, taking care to observe plug pin
polarity.

Table of Contents

Related product manuals