E6582062
11-31 11. Table of parameters
1
3
9
10
11
F592 0592
Shock monitoring
detection
0: Overcurrent/
Overtorque detection
1: Undercurrent/
Undertorque
detection
--0Y
[6. 29]
F593 0593
Shock monitoring
detection level
0 - 250 % 150 Y
F595 0595
Shock monitoring
detection time
0.0 - 10.0 s 0.5 Y
F596 0596
Shock monitoring
detection hysteresis
0 - 100 % 10 Y
F597 0597
Shock monitoring
detection wait time
0.0 - 300.0 s 0.0 Y
F598 0598
Shock monitoring
detection condition
0: During run
1: During run (except
Acc/Dec)
--0Y
F600 0600
Parameter for
manufacturer
------
F601 0601
Stall prevention
level 1
10 - 200 (HD)
10 - 160 (ND)
%
150 (HD)
120 (ND)
Y
[6. 24. 3]
[6. 30. 2]
F602 0602 Trip record retention
0: Clear at power off
1: Retain at power off
- - 0 Y [6. 30. 3]
F603 0603
Emergency off stop
pattern
0: Trip
1: Trip after Deceleration
stop
2: Trip after Emergency
DC braking
3: Trip after deceleration
stop by F515
4: Trip after Quick
deceleration stop
5: Trip after Dynamic
quick deceleration
stop
--0N
[6. 30. 4]
F604 0604
Emergency DC
braking time
0.0 - 20.0 s 1.0 Y
F605 0605
Output phase loss
detection
0: Disabled
1: At startup (only one
time after power on)
2: At every startup
3: During run
4: At every startup +
during run
5: Output shut off
detection
- - 0 N [6. 30. 5]
F606 0606
Motor overload
reduction frequency
threshold
0.0 - 60.0 Hz 6.0 Y
[5. 2. 5]
[6. 30. 1]
F607 0607 Motor overload time 10 - 2400 s 300 Y
F608 0608 Input phase loss trip
0: Disabled
1: Enabled
- - 1 N [6. 30. 6]