E6582062
11. Table of parameters 11-32
1
9
11
F609 0609
Undercurrent
detection hysteresis
1 - 20 % 10 Y
[6. 30. 7]
F610 0610 Undercurrent trip
0: Disabled
1: Enabled
--0Y
F611 0611
Undercurrent
detection level
0 - 150 % 0 Y
F612 0612
Undercurrent
detection time
0 - 255 s 0 Y
F613 0613
Short circuit
detection at start
0: At every startup by
standard pulse
1: Only one time after
power on by standard
pulse
2: At every startup by
F614 setting pulse
3: Only one time after
power on by F614
setting pulse
--0N
[6. 30. 9]
F614 0614
Pulse width of short
circuit detection at
start
0: No short circuit
detection at start
1 - 50
μs25N
F615 0615 Overtorque trip
0: Disabled
1: Enabled
--0Y
[6. 30. 8]
F616 0616
Overtorque
detection level
during power
running
0: Disabled
1 - 320
% 150 Y
F617 0617
Overtorque
detection level
during regen
0: Disabled
1 - 320
% 150 Y
F618 0618
Overtorque
detection time
0.0 - 10.0 s 0.5 Y
F619 0619
Overtorque
detection hysteresis
0 - 100 % 10 Y
F620 0620 Cooling fan control
0: Auto ON/OFF, No
failure detection
1: Always ON, No failure
detection
2: Auto ON/OFF, Failure
detection
3: Always ON, Failure
detection
4 - 7: -
- - 2 Y [6. 30. 11]
F621 0621
Cumulative run time
alarm
0.0 - 999.0 100 h 876.0 Y [6. 30. 12]
F622 0622
Abnormal speed
detection time
0.01 - 100.0 s 0.01 Y
[6. 30. 13]F623 0623
Abnormal speed
increase band
0.00: Disabled
0.01 - 30.0
Hz 0.00 Y
F624 0624
Abnormal speed
decrease band
0.00: Disabled
0.01 - 30.0
Hz 0.00 Y
F625 0625
Undervoltage
detection level
50 - 79
80: Auto
%80N
[6. 15. 2]
[6. 30. 14]
Title
Communication
No.
Parameter name Adjustment range Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference