E6582062
11-33 11. Table of parameters
1
3
9
10
11
F626 0626
Overvoltage limit
operation level
100 - 150 % 134 N
[6. 15. 4]
[6. 15. 5]
F627 0627 Undervoltage trip
0: Disabled
1: Enabled
--0N
[6. 30. 14]
F628 0628
Undervoltage
detection time
0.01 - 10.00 s 0.03 N
F629 0629
Regenerative power
ride-through level
55 - 100 % 75 N
[6. 15. 2]
[6. 30. 14]
F630 0630
Brake answer wait
time
0.0: Disabled
0.1 - 10.0
s0.0Y
[6. 18. 1]
[6. 30. 15]
F631 0631
Inverter overload
detection
0: 150% - 60s (HD)
120% - 60s (ND)
1: Temperature
estimation
--0N
[5. 3. 5]
[6. 30. 1]
F632 0632
Motor overload
memory target
0: No.1 to 4 motor,
memory disabled
1: No.1 to 4 motor,
memory enabled
2: No.1 motor, memory
disabled
3: No.1 motor, memory
enabled
--0Y
F633 0633
II analog input
disconnection
detection level
0: Disabled
1 - 100
% 0 Y [6. 30. 16]
F634 0634
Annual average
ambient
temperature
1: -15 to +10°C
2: +11 to +20°C
3: +21 to +30°C
4: +31 to +40°C
5: +41 to +50°C
6: +51 to +60°C
- - 3 Y [6. 30. 17]
F635 0635
Rush current
suppression relay
delay time
0.0 - 2.5 s 0.0 N [6. 30. 18]
F636 0636 Ground fault trip
0: Disabled
1: Enabled
- - 1 N [6. 30. 10]
F637 0637
Terminal AI4 PTC
trip
0: Disabled
1: Enabled
--0N
[6. 30. 19]
F638 0638
Terminal AI5 PTC
trip
0: Disabled
1: Enabled
--0N
F639 0639
Braking resistor
overload time
0.1 - 600.0 s 5.0 N [6. 15. 4]
F640 0640 DC supply input
0: Disabled
1: Enabled
--0N -
F643 0643
Residual voltage
waiting control
frequency threshold
0.0 - 60.0 Hz 10.0 N -
F644 0644
Operation after II
analog input
disconnection
detection
1: Continue running
2: Deceleration stop
3: Coast stop
4: Trip
5: Run by F649
- - 4 N [6. 30. 16]
Title
Communication
No.
Parameter name Adjustment range Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference