5.2.4 Mode: PGM (500)
Switch position: 500
The PGM-mode enables access of the Turck DTMs to the device’s network settings.
5.2.5 Mode: PGM-DHCP (600)
Switch position: 600
The device sends DHCP-requests until a IP address is assigned (DHCP-server, PROFINET-controller).
The assigned IP-address is stored to the device and the DHCP-client is stopped.
Even after a restart of the device, the device sends no further DHCP-requests.
PROFINET
This mode assures a PROFINET-compliant operation of the modules.
5.2.6 Resetting the IP Address, Switch Position "000"
With this setting the DIP-switches to "000" followed by a voltage reset, the device is set to the
address 192.168.1.254 for IP-based services (see Default Setting of the Device, page 21).
NOTE
In the PGM-mode, all network settings (IP address, subnet mask, etc.) are send to the
device’s internal EEPROM and stored permanently.
NOTE
If a DHCP-server is used within the network, problems may occur during IP-assignment.
In this case, both, the DHCP-server as well as the PROFINET-controller (via DCP), try an IP-
address-assignment.
NOTE
Setting "000" is no operation mode! After having reset the IP address to the default values,
the device has to be set to another mode.