11.6.3 Process Data Instances
Instance 101
Contains the device’s input data (static length 256 bytes).
2 Bytes status information
+ process data
Instance 102
Contains the device’s output data (static length 256 bytes).
2 bytes control data (mapped, but not defined)
+ process data
Instance 103 and Instance 104
In- and output assembly instances with variable assembly sizes. The assembly size is pre-calculated
to support the stations I/O-configuration, enabled diagnostics, etc.
Input Assembly Instance: 103
Output Assembly Instance: 104
The effective size of the Assembly Instance can be determined using the Assembly Object (
instance
0×67, attribute 0x04) and can be from 2 to 496 bytes large.
Process Data Mapping TBEN-Lx-16DIP/TBEN-L4-16DIN
Scheduled diagnostic data mode
Default setting, see page 67
Meaning of the Process Data Bits, page 84.
IN = 8 byte
OUT = 2 byte
IN Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Status 0
V
2
------
Diag
Warn
1
- FCE - - CFG COM V
1
-
Inputs 2
DI7
C3P2
DI6
C3P4
DI5
C2P2
DI4
C2P4
DI3
C1P2
DI2
C1P4
DI1
C0P2
DI0
C0P4
3
DI15
C7P2
DI14
C7P4
DI13
C6P2
DI12
C6P4
DI11
C5P2
DI10
C5P4
DI9
C4P2
DI8
C4P4
Diagnos-
tics
3
-------I/O Diag
4
--
Sched
Diag
-----
5
SCS7 SCS6 SCS5 SCS4 SCS3 SCS2 SCS1 SCS0
6
--------
OUT Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Control 0
Control word (MSB)
1
Control word (LSB)