Name Value Meaning
DXPx
FBI1.x
CxPy
These input bits of the IO-Link channels are map
ped into the device's PROFIsafe out-
put data and are provided as fieldbus bits (1-4, 1-5, 1-6 and 1-7) in the Turck Safety
Configurator.
0 Input active
1 Input active
DVSx Input value valid (Data Valid Signal)
0 The IO-Link data are valid.
Possible causes:
– Sensor supply is below the admissible range,
– IO-Link port is parameterized as simple digital input,
– No device connected to the masters,
– No input data received from the connected device (only valid for devices with an
input data length > 0),
– No reaction from the connected device to the sending of output data (only valid
for devices with an output data length > 0),
– The connected device sends an error "process input data invalid.
1 The IO-Link data are valid.
SCOx Overcurrent output
0 No overcurrent
1 Overcurrent at the output (if the D
XP channel is used as output)
IO-Link process input data
Process input data of the connected device
The order of the IO-Link process input data can be changed via the parameter "Process input data mapping"
(
page 17).
15
V01.0| 2017/04
TBPN-L1-FDIO1-2IOL - Standard IO-Link