71
V01.00| 2017/04

TBPN-L1-FDIO1-2IOL- Safe I/O channels
PROFINET input data (Status of the safe unit)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n + 7
FBO07 FBO06 FBO05 FBO04 FBO03 FBO02 FBO01 FBO00
Name
FBO00 to FBO07 Status output bits of the safe unit of TBPN-L1-FDIO1-2IOL which can be used as input
signals for the non-safety part of the higher level control.
These bits have to be configured by the user in Turck Safety Configurator.
Fig. 45: Output assignment in Turck Safety Configurator
PROFIsafe Error Codes
Code Name Meaning Remedy
64
(0x40)
Destination
Ad
dress Mismatch
Destination
Ad
dress
The set PROFIsafe address does not
matc
h the parameterized destina-
tion address (F_DEST_ADDR).
hChange the parameter
¬Restart the device
65
(0x41)
Invalid
Destination
Ad
dress
The set destination address
(F_DEST_ADDR) is not valid.
Addresses 0x0000 and 0xFFF are not
allowed.
hChange the parameter
¬Restart the device
66
(0x42)
Invalid
Source Address
The set source address
(F_SOUR
CE_ADDR) is not valid.
Addresses 0x0000 and 0xFFF are not
allowed.
hChange the parameter
¬Restart the device
67
(0x43)
Invalid Watchdog
Time Value
Invalid value for watchdog time
(F_WD_
Time, F_WD_Time 2). A
watchdog time of 0 ms is not
allowed.
hChange the parameter
¬Restart the device

Table of Contents