Memory and F-Config Status
Name Code Meaning
PMS 512 No Memory Chip Plugged
NCNF 513 No Configuration Available
CNFMV 514 Configuration Mismatch
COMLO 516 Communication loss
FERR 519 Fatal Error
Safe Status (connector C0 - C7)
Name Code Meaning
RGG Normal State
WAIT 528 Wait for input signal
TEST 544 Test input
ERRFIN 560 Error at input
TCCH0 576 Cross-circuit channel 0
TCCH1 592 Cross-circuit channel 1
68
(0x44)
SIL Value
Exceeded
The required SIL level is not sup-
ported by the device.
hParameter change
¬Device restart
69
(0x45)
Invalid
Length of CRC2
The required CRC length and the CRC
length
generated by the device do
not match.
hCheck parameterization
70
(0x46)
Invalid PROFIsafe
version
The version of the F_parameter set is
invali
d.
hCheck parameterization
71
(0x47)
CRC1 Mismatch The CRC1 generated by the device
d
oes not match the CRC1 in the
parameter telegram
hCheck the configuration in
PROFIsafe
72
(0x48)
Destination
Ad
dress Mismatch
PROFIsafe
Parameters
Device specific or undefined diag-
nostic information
75
(0x4B)
Wrong iParameter
CRC
The iParCRC from the device and the
iPa
rCRC in the PROFIsafe configura-
tion do not match.
hCheck the configuration in
PROFIsafe
Code Name Meaning Remedy