100 Use in Hazardous Environments WAGO I/O System 750 XTR
750-677/040-000 4PWM 24 VDC 0.2A XTR
Manual
Version 1.0.0
10.2.2 Special Notes Regarding UL Hazardous Location
For UL Hazardous Location acc. to UL File E198726, the following additional
requirements apply:
Use in Class I, Division 2, Group A, B, C, D or non-hazardous areas only
ETHERNET connections are used exclusively for connecting to computer
networks (LANs) and may not be connected to telephone networks or
telecommunication cables
WARNINGThe radio receiver module 750-642 may only be used to
connect to external antenna 758-910!
WARNINGProduct components with fuses must not be fitted into circuits
subject to overloads!
These include, e.g., motor circuits.
WARNINGWhen installing I/O module 750-538, “Control Drawing No.
750538” in the manual must be strictly observed!
Additional Information
Proof of certification is available on request.
Also take note of the information given on the operating and assembly
instructions.
The manual, containing these special conditions for safe use, must be readily
available to the user.