EasyManua.ls Logo

WAGO 750 XTR - Figure 35: Data Dialog, Example 4

WAGO 750 XTR
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WAGO I/O System 750 XTR Commissioning 85
750-677/040-000 4PWM 24 VDC 0.2A XTR
Manual
Version 1.0.0
Example 4:
Channel 1/2: PWM Frq-Cnt
Channel 3/4: PWM Pulse-Dir
Figure 33: Data Dialog, Example 4
The complex operating mode “PWM Frq-Cnt” is preset for Channel 1/2.
The function results from the interaction of both channels and is therefore
combined. The process data value (frequency) can be entered as a value. The
counter (actual value) is displayed and can be reset with the adjacent button ( ).
The counting direction is set by pressing the arrow keys ( ).
Channel pair 1/2 is enabled (checkbox selected), the associated output is
therefore not high-impedance.
The complex operating mode “PWM Pulse-Dir” is preset for Channel 3/4.
The function results from the interaction of both channels and is therefore
combined. The process data value (number of PWM cycles) can be entered as a
setpoint.
The counter (residual value) is displayed and can be:
Increased by the entered setpoint ( button) or
Set to the entered setpoint ( button).
The counting process is started by pressing one of the two arrow keys ( ).
In both cases, the count is decreased.
The right arrow key also sets the corresponding output DO 4 in the control
byte to “High”.
The left arrow key also sets the corresponding output DO 4 to “Low”.
The Stop button is used to stop the counting process.
Channel pair 3/4 is enabled (checkbox selected), the associated output is
therefore not high-impedance.

Table of Contents

Related product manuals