EasyManua.ls Logo

WAGO 750 XTR - Parameter Settings; Function of the Output Channels; Table 26: Status Byte 0 (PWM DC); Table 27: Status Byte 2 (PWM DC)

WAGO 750 XTR
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WAGO I/O System 750 XTR Operating Modes 45
750-677/040-000 4PWM 24 VDC 0.2A XTR
Manual
Version 1.0.0
Control bytes 1 and 3 can be permanently “0” and have no influence on the
system.
Table 26: Status Byte 0 (PWM DC)
Status byte 0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg
Com
General Error
Bit
Undervoltage
Short circuit
DO 1 or DO 2
- - -
Enable DO 1 &
DO 2 Drivers
Legend
Enable DO 1 & DO 2
Drivers
0: The status of the output driver for DO 1 & DO 2 is disabled.
1: The status of the output driver for DO 1 & DO 2 is enabled.
Short circuit DO 1 or
DO 2
0: There is no short circuit at outputs DO 1 or DO 2.
1: There is a short circuit at output DO 1 or DO 2.
Undervoltage
0: There is no undervoltage on the I/O module.
1: There is an undervoltage on the I/O module.
General Error Bit
0: There is no error.
1: There is an undervoltage or a short circuit.
Bits 0-3 are masked out.
RegCom
0: Register communication is disabled (normal mode).
1: Register communication is enabled.
Table 27: Status Byte 2 (PWM DC)
Status byte 2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg
Com
General Error
Bit
Undervoltage
Short circuit
DO 3 or DO 4
- - -
Enable DO 3 &
DO 4 Drivers
Legende
Enable DO 3 & DO 4
Drivers
0: The status of the output driver for DO 3 & DO 4 is disabled.
1: The status of the output driver for DO 3 & DO 4 is enabled.
Short circuit DO 3 or
DO 4
0: There is no short circuit at outputs DO 3 or DO 4.
1: There is a short circuit at output DO 3 or DO 4.
Undervoltage
0: There is no undervoltage on the I/O module.
1: There is an undervoltage on the I/O module.
General Error Bit
0: There is no error.
1: There is an undervoltage or a short circuit.
Bits 0-3 are masked out.
RegCom
0: Register communication is disabled (normal mode).
1: Register communication is enabled.
Status byte 1 and 3 are permanently “0”.
4.1.2 Parameter Settings
The frequency can be preset in the range from 1 Hz to 20,000 Hz.
When switching on for the first time, the default value of 250 Hz is loaded for this
parameter.
4.1.3 Function of the Output Channels
Output 1 (DO 1): Output signal 1
Output 2 (DO 2): Output signal 2

Table of Contents

Related product manuals