3.6 Device-specific Settings
3.6.2 Detailed Module Settings
3-30
SIZE
Set the input and output sizes in words.
These settings are disabled if the profile is set to Standard Servo.
Setting range: 0 to 32
SCAN
Set the scan in which the input and output is performed.
This setting is always set to High if the profile is set to Standard Servo.
Settings: High or Low
Comment
Enter a comment of up to 32 characters if required.
Deleting Station Assignments
You can delete the items on the Link Assignment Tab Page for a station.
Click any cell in the row for the station to delete, and then select Edit Assignment Delete
from the menu bar.
Deleted station assignments cannot be restored.