A.2 MP3300 Installation and Usage Conditions
A.2.2 Mechanical Operating Conditions
A-7
AppA
Controller Specifications
A.2.2
Mechanical Operating Conditions
A.2.3
Electrical Operating Conditions
A.2.4
Installation Conditions
Item Specification
Vibration Resistance
Conforms to JIS B 3502.
• Continuous Vibration:
Frequency: 5 to 8.4 Hz, Single amplitude: 1.75 mm,
Frequency: 8.4 to 150 Hz, Fixed acceleration: 4.9 mm/s
2
• Intermittent Vibration:
Frequency: 5 to 8.4 Hz, Single amplitude: 3.5 mm
Frequency: 8.4 to 150 Hz, Fixed acceleration: 9.8 mm/s
2
10 sweeps each in X, Y, and Z directions for both intermittent and continuous
vibration
Shock Resistance
Size of shock: Peak acceleration of 147 m/s
2
(15 G)
Duration: 11 ms
3 times each in X, Y, and Z directions
Item Specification
Noise Resistance
Conforms to EN 61000-6-2 and EN 55011 (Group 1 Class A).
Power supply noise (FT noise): ±2 kV min. for one minute
Radiation noise (FT noise): ±1 kV min. for one minute
Ground noise (impulse noise): ±1 kV min. for 10 minutes
Electrostatic noise (contact discharge method): ±6 kV or more, 10 times
Item Specification
Ground Ground to 100 Ω max.
Cooling Method Natural cooling or forced-air cooling