EasyManuals Logo

YASKAWA T1000V User Manual

YASKAWA T1000V
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #105 background imageLoading...
Page #105 background image
5.1 A: Initialization
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 105
Parameter Details
5
Table 5.4 Enter the Password to Unlock Parameters (continuing from step 4 above)
Note: Parameter settings can be edited after entering the correct password. Performing a 2-Wire or 3-Wire initialization resets the
password to “0000”. Reenter the password to parameter A1-05 after drive initialization.
A2: User Parameters
A2-01 to A2-32: User Parameters 1 to 32
The user can select 32 parameters and assign them to A2-01 through A2-32. This saves time later scrolling through the
parameter menu. The list of User Parameters can also track the most recently edited settings and save those parameters to
this list.
Saving User Parameters
To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-02 = 2).
Next assign the parameter number to the User Parameters list by entering it into one of the A2- parameters. By then
setting A1-01 to “1”, the access level can be restricted so that users can only set and reference the specific parameters
saved as User Parameters.
A2-33: User Parameter Automatic Selection
A2-33 determines whether or not parameters that have been edited are saved to the User Parameters (A2-17 to A2-32) for
quick, easy access.
Setting 0: Do not save list of recently viewed parameters.
To manually select the parameters listed in the User Parameter group, set A2-33 to “0”.
Setting 1: Save history of recently viewed parameters.
By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A
total of 16 parameters are saved in order with the most recently edited parameter set to A2-17. User parameters can be
accessed using the Setup mode of the digital operator.
Step Display/Result
1.
Press to enter the parameter setup display.
2.
Press to select the flashing digits as shown.
“01” flashes
3.
Press to scroll to A1-04.
4. Enter the password “1234”.
5.
Press to save the new password.
6. Drive returns to the parameter display.
7.
Press and scroll to A1-01.
8.
Press to display the value set to A1-01. If the first "0" blinks, parameter settings
are unlocked.
9.
Use and to change the value if desired. This is not typical.
10.
Press to save the setting, or to return to the previous display without saving
changes.
11. The display automatically returns to the parameter display.
No. Parameter Name Setting Range Default
A2-01 to A2-32 User Parameters 1 to 32 A1-00 to o2-08
No. Parameter Name Setting Range Default
A2-33 User Parameter Automatic Selection 0 or 1 1