EasyManua.ls Logo

YASKAWA T1000V - Subchart A1: Simple Motor Setup with Energy Savings or Speed Search Using V;F Mode; Subchart A2: High Performance Operation Using Open Loop Vector Motor Control

YASKAWA T1000V
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.4 Start-up Flowcharts
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 85
Start-Up Programming
& Operation
4
Subchart A1: Simple Motor Setup with Energy Savings or Speed Search Using V/f
Mode
Figure 4.7, Flowchart A1, describes simple motor setup for V/f control. This procedure illustrates using Energy Savings
and Speed Estimation Speed Search. V/f control can be used where rotational auto-tuning cannot be performed.
Figure 4.7
Figure 4.7 Simple Motor Set-Up with Energy Savings or Speed Search Using V/f Mode
Subchart A2: High Performance Operation Using Open Loop Vector Motor Control
Figure 4.8, Flowchart A2, describes Open Loop Vector Control for high-performance motor operation. This is
appropriate for applications requiring high starting torque, torque limits, and improved speed regulation.
Figure 4.8
Figure 4.8 Flowchart A2: High Performance Operation Using Open Loop Vector Motor Control
From
Flowchart
A
Set or verify the V/f pattern settings E1-.
Energy Savings
(b8-01=1)
or
Speed Estimation
Speed Search (b3-24=1)
enabled ?
Is the motor cable
longer than 50 m?
Perform Rotational Auto-Tuning
for V/f Control
(T1-01 = 3
)
NO
YES
Perform Stationary Auto-Tuning for
terminal resistance (T1-01 = 2
)
YES
NO
Return to
Flowchart
A
From
Flowchart
A
Possible for motor to
rotate during tuning? <1>
<1>
Rotational tuning should
be performed with the
load disconnected
NO YES
NO
Motor test report/ data
sheet available?
NO
YES
YES
Perform Rotating Auto-
Tuning (T1-01 = 0)
Is the motor cable
longer than 50 m?
Perform Stationary Auto-Tuning for
terminal resistance (T1-01 = 2)
Enter the data from the motor data
sheet to E2- parameters.
Calculate necessary E2-
parameter data using the
nameplate information.
Return to
Flowchart
A

Table of Contents

Related product manuals