EasyManua.ls Logo

YASKAWA T1000V - I;O Connections; Sinking;Sourcing Mode Switch

YASKAWA T1000V
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
3.8 I/O Connections
3.8 I/O Connections
Sinking/Sourcing Mode Switch
Set the DIP switch S3 on the front of the drive to switch the digital input terminal logic between sinking mode and
sourcing mode; the drive is preset to sinking mode.
Table 3.11 Sinking/Sourcing Mode Setting
Figure 3. 18
Figure 3.18 DIP Switch S3
Transistor Input Signal Using 0 V Common/Sink Mode
When controlling the digital inputs by NPN transistors (0 V common/sinking mode), set the DIP switch S3 to SINK and
use the internal 24 V power supply.
Figure 3. 19
Figure 3.19 Sinking Mode: Sequence from NPN Transistor (0 V Common)
Set Value Details
SINK Sinking Mode (0 V common): default setting
SOURCE Sourcing Mode (+24 V common)
DIP Switch S3
SINK
SOURCE
Drive
Shielded cable
Forward run/stop
Reverse run/stop
External fault N.O.
Fault reset
Multi-speed step 1
Multi-speed step 2
Multi-function input
S1
SINK
SOURCE
S2
S3
S3
+24V
S4
S5
S6
SC
SINK
SOURCE

Table of Contents

Related product manuals