A.2 Single/Three-Phase 200 V Class Drive
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 309
A.2 Single/Three-Phase 200 V Class Drive
Table A.2 Power Ratings
Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output
current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to “0” (default) for HD or “1” for ND.
Item
<1> Drives with a single-phase power supply input output three-phase power, and cannot run a single-phase motor.
<2> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor rated current.
<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency.
<7> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
Specification
Three-Phase: CIMR-TC2V 0001 0002 0004 0006 0010 0012 0020 0030 0040 0056 0069
Single-Phase: CIMR-TCBV <1> 0001 0002 0003 0006 0010 0012 – – – – –
Maximum Motor Size Allowed (kW) <2>
HD Rating 0.1 0.2 0.4 0.75 1.5 2.2 4.0 5.5 7.5 11.0 15.0
ND Rating 0.2 0.4 0.75 1.1 2.2 3.0 5.5 7.5 11.0 15.0 18.5
Input
Input Current
(A)
<3>
Three-Phase
HD Rating 0.7 1.5 2.9 5.8 7.5 11.0 18.9 24.0 37.0 52.0 68.0
ND Rating 1.1 1.9 3.9 7.3 10.8 13.9 24.0 37.0 52.0 68.0 80.0
Single-
Phase
HD Rating 1.4 2.8 5.5 11.0 14.1 20.6 35.0 – – – –
ND Rating 2.0 3.6 7.3 13.8 20.2 24.0 – – – – –
Output
Rated Output Capacity
(kVA)
<4>
HD Rating 0.3 0.6 1.1 1.9 3.0 4.2 6.7 9.5 12.6 17.9 22.9
ND Rating 0.5 0.7 1.3 2.3 3.7 4.6 7.5 11.4 15.2 21.3 26.3
Output Current (A)
HD Rating 0.8 <6> 1.6 <6> 3.0 <6> 5.0 <6> 8.0 <7> 11.0 <7> 17.5 <7> 25.0 <7> 33.0 <7> 47.0 <7> 60.0 <7>
ND Rating
<5>
1.2 1.9
3.5
(3.3)
6.0 9.6 12.0 19.6 30.0 40.0 56.0 69.0
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User adjustable between 2 and 15 kHz (see HD output current line of this table for
default values)
Max Output Voltage (V) Three-phase 200 to 240 V (proportional to input voltage)
Max Output Frequency (Hz) 400 Hz (user-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase power: Three-phase 200 to 240 V 50/60 Hz
Single-phase power: 200 to 240 V 50/60 Hz
Allowable Voltage Fluctuation –15 to 10%
Allowable Frequency Fluctuation ±5%
Harmonic Corrective
Actions
DC Reactor Optional
Total Loss (W)
Three-Phase
HD Rating 11.6 16.7 27.6 43.3 78.6 100.7 153.8 281.4 319.1 461.4 630.6
ND Rating 13.0 17.1 29.4 44.7 77.5 91.7 145.0 324.0 375.3 503.1 663.1
Single-
Phase
HD Rating 11.7 16.8 27.6 50.5 80.7 104.8 – – – – –
ND Rating 13.5 17.3 29.0 49.5 81.5 98.4 – – – – –