B.3 Parameter Table
326 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, slip and torque compensation functions
and carrier frequency selections.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M
C1: Acceleration and Deceleration Times
Use C1 parameters to configure motor acceleration and deceleration.
C1-01
<15>
Acceleration Time 1
Sets the time to accelerate from 0 to maximum
frequency.
0.0 to
6000.0
<5>
10.0 s
S S S 200 133
C1-02
<15>
Deceleration Time 1
Sets the time to decelerate from maximum frequency to
0.
S S S 201 133
C1-03
<15>
Acceleration Time 2
Sets the time to accelerate from 0 to maximum
frequency when Accel/Decel times 2 are selected by a
digital input.
A A A 202 133
C1-04
<15>
Deceleration Time 2
Sets the time to decelerate from maximum frequency to
0 when Accel/Decel times 2 are selected by a digital
input.
A A A 203 133
C1-05
<15>
Acceleration Time 3 (Motor
2 Accel Time 1)
Sets the time to accelerate from 0 to maximum
frequency when Accel/Decel times 3 are selected by a
digital input.
A A A 204 133
C1-06
<15>
Deceleration Time 3 (Motor
2 Decel Time 1)
Sets the time to decelerate from maximum frequency to
0 when Accel/Decel times 3 are selected by a digital
input.
A A A 205 133
C1-07
<15>
Acceleration Time 4 (Motor
2 Accel Time 2)
Sets the time to accelerate from 0 to maximum
frequency when Accel/Decel times 4 are selected by a
digital input.
A A A 206 133
C1-08
<15>
Deceleration Time 4 (Motor
2 Decel Time 2)
Sets the time to decelerate from maximum frequency to
0 when Accel/Decel times 4 are selected by a digital
input.
A A A 207 133
C1-09 Fast-Stop Time
Sets the time to decelerate from maximum frequency to
0 for the multi-function input fast-stop function.
Note: This parameter is also used by selecting “Fast-
Stop” as a Stop Method when a fault is detected.
0.0 to
6000.0
<5>
10.0 s A A A 208 134
C1-10
Accel/Decel Time Setting
Units
Sets the resolution of C1-01 to C1-09.
0: 0.01 s (0.00 to 600.00 s)
1: 0.1 s (0.0 to 6000.0 s)
0, 1 1 A A A 209 134
C1-11
Accel/Decel Time
Switching Frequency
Sets the frequency for automatic acceleration/
deceleration switching.
Below set frequency: Accel/Decel Time 4
Above set frequency: Accel/Decel Time 1
The multi-function input “Accel/Decel Time 1” or
“Accel/Decel Time 2” take priority.
0.0 to 400.0
Hz
0.0 Hz A A A 20A 135
C2: S-Curve Characteristics
Use C2 parameters to configure S-curve operation.
C2-01
<15>
S-Curve Characteristic at
Accel Start
The S-curve can be controlled in the four points shown
below.
S-curve is used to further soften the starting and
stopping ramp. The longer the S-curve time, the softer
the starting and stopping ramp.
0.00 to
10.00
0.20 s
<2>
A A A 20B 135
C2-02
<15>
S-Curve Characteristic at
Accel End
0.00 to 10.0 0.20 s A A A 20C 135
C2-03
<15>
S-Curve Characteristic at
Decel Start
0.00 to 10.0 0.20 s A A A 20D 135
C2-04
<15>
S-Curve Characteristic at
Decel End
0.00 to 10.0 0.00 s A A A 20E 135
Run
command
Output
frequency
Time
C2-01
C2-04
C2-02
C2-03
ON
OFF