102 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
5.1 A: Initialization
5.1 A: Initialization
The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display
language, access levels, initialization, and password are located in this group.
A1: Initialization
A1-00: Language Selection
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
Setting 0: Operation Only
Access is restricted to parameters A1-01, A1-04, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
Notes on Parameter Access
If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, and all A2
parameters cannot be modified.
If a digital input programmed for Program Lockout (H1- = 1B) is enabled, parameter values can not be modified,
even though the A1-01 is set to 1 or 2.
If parameters are changed via serial communication the parameters can not be changed from the digital operator until
an Enter command is received from the serial communication.
A1-02: Control Mode Selection
Selects the Control Method of the drive.
Note: 1. Auto-Tuning must be performed on the motor when A1-02 = 2, 5.
2. This parameter is not reset when the drive is initialized using parameter A1-03.
Setting 0: V/f Control
For general-purpose and multiple motor applications.
For use when the motor parameters are unknown and Auto-tuning can not be performed.
No. Parameter Name Setting Range Default
A1-00 Language Selection 0 to 7 0
No. Parameter Name Setting Range Default
A1-01 Access Level Selection 0 to 9999 2
No. Parameter Name Setting Range Default
A1-02 Control Method Selection 0, 2, 5 0