C.10 MEMOBUS/Modbus Data Table
396 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Monitor Data
Monitor data can be read only.
Register No. Contents
0020H
Drive Status 1
bit 0 During Run
bit 1 During Reverse
bit 2 Drive Ready
bit 3 Fault
bit 4 Data Setting Error
bit 5 Multi-Function Contact Output (terminal MA/MB-MC)
bit 6 Multi-Function Photocoupler Output 1 (terminal P1 - C1)
bit 7 Multi-Function Photocoupler Output 2 (terminal P2 - C2)
bit 8 to bit D Reserved
bit E ComRef status
bit F ComCtrl status
0021H
Fault Contents 1
bit 0 Overcurrent (oC), Ground fault (GF)
bit 1 Overvoltage (ov)
bit 2 Drive Overload (oL2)
bit 3 Overheat 1 (oH1), Drive Overheat Warning (oH2)
bit 4 Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH)
bit 5 Reserved
bit 6 Overcurrent (oC), Ground Fault (GF)
bit 7 EF0 to 6: External Fault
bit 8 CPF: Hardware Fault (includes oFx)
bit 9
Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2
(UL3/UL4)
bit A PG Disconnected (PGo), Overspeed (oS), Excessive Speed Deviation (dEv),
bit B Main Circuit Undervoltage (Uv)
bit C
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault
(Uv3)
bit D Output Phase Loss (LF), Input Phase Loss (PF)
bit E MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
bit F Operator Connection Fault (oPr)
0022H
Data Link Status
bit 0 Writing data or switching motors
bit 1
Reserved
bit 2
bit 3 Upper or lower limit error
bit 4 Data conformity error
bit 5 Writing to EEPROM
bit 6 to bit F Reserved
0023H Frequency Reference, <1>
0024H Output Frequency, <1>
0025H Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)
0026H Output Current (0.1 A units), <2>
0027H Output Power
0028H Torque Reference (OLV only)
0029H
Fault Contents 2
bit 0 Reserved
bit 1 Ground Fault (GF)
bit 2 Input Phase Loss (PF)
bit 3 Output Phase Loss (LF)
bit 4 Braking Resistor Overheat (rH)
bit 5 Reserved
bit 6 Motor Overheat 2 (PTC input) (oH4)
bit 7 to bit F Reserved