B.5 V/f Pattern Default Values
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 365
B.5 V/f Pattern Default Values
The tables below show the V/f pattern settings default values depending on the Control Method Selection (A1-02).
Table B.3 V/f Pattern Selection for Drive Capacity: CIMR-TCBV0001 to CIMR-TCBV0010;
CIMR-TC2V0001 to CIMR-TC2V0010; CIMR-TC4V0001 to CIMR-TC4V0005
Table B.4 V/f Pattern Selection for Drive Capacity: CIMR-TCBV0012
CIMR-TC2V0012 to CIMR-TC2V0069; CIMR-TC4V0007 to CIMR-TC4V0038
No.
<9> Default setting is determined by the motor code set to parameter E5-01.
<17> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<32> Numbers appearing in this column are the default values set to parameters E1-04 through E1-10 and E2-04 through E2-10.
Unit V/f OLV PM
E1-03 − F <32>
E1-04 Hz 50.0 50.0 <9>
E1-05 <17> V 200 200 <9>
E1-06 Hz 50.0 50.0 <9>
E1-07 Hz 2.5 3.0 –
E1-08 <17> V 16.0 14.4 –
E1-09 Hz 1.3 0.5
<9>
E1-10 <17> V 12.0 3.0 –
No.
<9> Default setting is determined by the motor code set to parameter E5-01.
<17> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<32> Numbers appearing in this column are the default values set to parameters E1-04 through E1-10 and E2-04 through E2-10.
Unit V/f OLV PM
E1-03 − F <32>
E1-04 Hz 50.0 50.0 <9>
E1-05 <17> V 200 200 <9>
E1-06 Hz 50.0 50.0 <9>
E1-07 Hz 2.5 3.0 –
E1-08 <17> V 14.0 13.2 –
E1-09 Hz 1.3 0.5
<9>
E1-10 <17> V7.0 2.4 –