5.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 153
Parameter Details
5
E4-06: Motor 2 Leakage Inductance
Sets the voltage drop due to motor leakage inductance of motor 2. The value is set as a percentage of the rated voltage.
E4-10: Motor 2 Iron Loss
Sets the motor 2 iron loss in watts.
E4-11: Motor 2 Rated Power
Sets the motor 2 rated power. During Auto-Tuning the value must entered to parameter T1-02. If Auto-Tuning completes
successfully, the entered value will automatically be saved to E4-11.
E4-14: Motor 2 Slip Compensation Gain
Instead of C3-01 the value of E4-14 is used as gain for slip compensation when motor 2 is selected. Refer to C3-01: Slip
Compensation Gain on page 136 for details and setting instructions.
E4-15: Motor 2 Torque Compensation Gain
Instead of C4-01 the value of E4-15 is used as gain for torque compensation when motor 2 is selected. Refer to C4-01:
Torque Compensation Gain on page 137 for details and setting instructions.
E5: PM Motor Settings
These parameters set the motor data of a PM motor used in OLV for PM (A1-02 = 5).
When Yaskawa motors are used, entering the motor code written on the motor nameplate will set up the E5-
parameters. For all other PM motors, the data must be entered manually.
E5-01: PM Motor Code Selection
Set the motor code for the PM motor being used. Depending on the motor code entered, the drive automatically sets
several parameters to appropriate values. Refer to E5-01 (PM Motor Code Selection) Dependent Parameters on
page 374 for details on the supported motor codes and their parameter settings.
Note: 1. This parameter is not reset when the drive is initialized using parameter A1-03.
2. The default setting is for a Yaskawa SMRA Series SPM Motor with a speed rating of 1800 r/min.
3. Changing the motor code setting resets all E5- settings to their default values.
4. Set to “FFFF” when using a non-Yaskawa PM motor or one that is not supported by the motor code settings.
No. Parameter Name Setting Range Default
E4-06 Motor 2 Leakage Inductance 0.0 to 40.0%
Determined by
C6-01 and o2-04
No. Parameter Name Setting Range Default
E4-10 Motor 2 Iron Loss 0 to 65535 W
Determined by
C6-01 and o2-04
No. Parameter Name Setting Range Default
E4-11 Motor 2 Rated Power 0.00 to 650.00 kW
Determined by
C6-01 and o2-04
No. Parameter Name Setting Range Default
E4-14 Motor 2 Slip Compensation Gain 0.0 to 2.50
Determined by
E3-01
No. Parameter Name Setting Range Default
E4-15 Motor 2 Torque Compensation Gain 0.0 to 2.50 1.00
No. Parameter Name Setting Range Default
E5-01 PM Motor Code Selection 0000 to FFFF
Determined by
o2-04