D.2 European Standards
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 411
■ Guarding Against Harmful Materials
When installing IP20/IP00 drives, use an enclosure that prevents foreign material from entering the drive from above or
below.
■
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of
grounded systems, contact your dealer or Yaskawa for instructions.
◆ EMC Guidelines Compliance
This drive is tested according to European standards EN61800-3 and it complies with the EMC guidelines.
■
EMC Filter Installation
The following conditions must be met to ensure continued compliance with guidelines. Refer to EMC Filters on
page 414 for EMC filter selection.
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this
drive also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2. Place the drive and EMC noise filter in the same enclosure.
3. Use braided shield cable for the drive and motor wiring or run the wiring through a metal conduit.
4. Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
Figure D.2
Figure D.2 Installation Method
Three-Phase 400 V Class
4V0001 A6T3 3 FWH-40B 40
4V0002 A6T6 6 FWH-40B 40
4V0004 A6T15 15 FWH-50B 50
4V0005 A6T20 20 FWH-70B 70
4V0007 A6T25 25 FWH-70B 70
4V0009 A6T25 25 FWH-90B 90
4V0011 A6T30 30 FWH-90B 90
4V0018
Not Available
FWH-80B 80
4V0023 FWH-100B 100
4V0031 FWH-125B 125
4V0038 FWH-200B 200
A – Drive D – Metal conduit
B – 20 m max cable length between drive and motor E – Ground wire should be as short as possible.
C – Motor
Drive Model CIMR-T
Non-Time Delay Class-T
Fuse Type
(Manufacturer: Ferraz)
600 Vac, 200 kAIR
Fuse Ampere Rating
(A)
Fuse Type
(Manufacturer: Bussmann)
500 Vac, 200 kAIR
Fuse Ampere Rating