D.2 European Standards
412 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
5. Ground the largest possible surface area of the shield to the metal conduit when using braided shield cable.
Yaskawa recommends using a cable clamp.
Figure D.3
Figure D.3 Ground Area
Three-Phase 200 V / 400 V Class
Figure D.4
Figure D.4 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)
A Braided shield cable C Cable clamp (conductive)
B–Metal panel
A Ground the cable shield F Motor cable (braided shield cable, max. 20 m)
B Enclosure panel G Motor
C Metal plate H Cable clamp
D Grounding surface (remove any paint or sealant) I Max. distance between drive and noise filter
E Drive J EMC noise filter