B.3 Parameter Table
336 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
ā H Parameters: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M
H1: Multi-Function Digital Inputs
H1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F".
H1-01
Multi-Function Digital Input Terminal S1 Function
Selection
Assigns a function to the multi-
function digital inputs.
Refer to H1 Multi-Function Digital
Input Selections on page 336 for a
description of setting values.
1 to 7E
<26>
40 (F)
<12>
A A A 438 159
H1-02
Multi-Function Digital Input Terminal S2 Function
Selection
41 (F)
<12>
A A A 439 159
H1-03
Multi-Function Digital Input Terminal S3 Function
Selection
0 to 7E
<26>
24 A A A 400 159
H1-04
Multi-Function Digital Input Terminal S4 Function
Selection
14 A A A 401 159
H1-05
Multi-Function Digital Input Terminal S5 Function
Selection
3 (0)
<12>
<12> Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization.
<26> The availability of certain functions depends on the control method used.
A A A 402 159
H1-06
Multi-Function Digital Input Terminal S6 Function
Selection
4 (3)
<12>
A A A 403 159
H1 Multi-Function Digital Inputs Settings
H1-īī
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
PM
0 3-Wire Sequence
Closed: Reverse rotation (only if the drive is set up for 3-Wire
sequence)
OOO160
1 LOCAL/REMOTE Selection
Open: REMOTE, Reference 1 or 2 (b1-01 and b1-02, or b1-15 and b1-
16)
Closed: LOCAL, LED operator is run and reference source
OOO160
2 External Reference 1/2
Open: Run and frequency reference source 1 (b1-01 and b1-02)
Closed: Run and frequency reference source 2 (b1-15 and b1-16)
OOO161
3 Multi-Step Speed Reference 1
Used to select Multi-Step Speeds set in d1-01 to d1-08
OOO161
4 Multi-Step Speed Reference 2 OOO161
5 Multi-Step Speed Reference 3 OOO161
6 Jog Reference Selection
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has priority over all other
reference sources.
OOO161
7 Accel/Decel Time 1 Used to switch between Accel/Decel. Time 1/2 O O O 161
8 Baseblock Command (N.O.)
Open: Normal operation
Closed: No drive output
OOO161
9 Baseblock Command (N.C.)
Open: No drive output
Closed: Normal operation
OOO161
A Accel/Decel Ramp Hold
Closed: The drive pauses during acceleration or deceleration and
maintains the output frequency.
OOO161
B Drive Overheat Alarm (oH2) Closed: Displays an oH2 alarm O O O 161
C Terminal A1/A2 Enable
Open: Terminal A1/A2 disabled
Closed: Terminal A1/A2 enabled
OOO162
F Not used
Select this setting when not using the terminal or when using the
terminal in a pass-through mode.
OOO162
10 Up Command
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency reference.
Ensure that the increase and decrease commands are set in conjunction
with one another.
OOO162
11 Down Command OOO162
12 Forward Jog Closed: Runs forward at the Jog Frequency d1-17. O O O 163
13 Reverse Jog Closed: Runs reverse at the Jog Frequency d1-17. O O O 163