5.10 o: Operator Related Settings
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 213
Parameter Details
5
5.10 o: Operator Related Settings
These parameters concern the various functions and features of the digital operator.
o1: Digital Operator Display Selection
These parameters determine how data is shown on the operator display.
o1-01: Drive Mode Unit Monitor Selection
When the drive is powered up, the monitor selected in parameter o1-02 appears first on the display. If o1-02 is set to 5,
o1-01 can be used to change the content of this monitor.
When using an LED operator, pressing the up arrow key will display the following data: speed reference rotational
direction output speed output current o1-01 selection.
Parameter o1-01 lets the user select the content of the last monitor in this sequence. There is no effect like this on an LCD
operator.
To select a monitor parameter, set the three numeric digits that make up that monitor. This is done by entering the -
part of U-. For a list of monitors, Refer to U: Monitor Parameters on page 230.
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter will be displayed upon power up. Defaulted to show the frequency reference when the
drive is first turned on.
Setting 1: Frequency Reference (U1-01)
Setting 2: Forward/Reverse
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Selected Monitor (set by o1-01)
o1-03: Digital Operator Display Selection
Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units, then set
parameters o1-10 and o1-11.
Setting 0: 0.01 Hz units
Setting 1: 0.01% units (100% = max. output frequency)
Setting 2: r/min units (calculated by the max output frequency and the no. of motor poles)
Setting 3: User-set units (use o1-10, o1-11)
Set the value use for the maximum frequency reference to o1-10. The placement of the decimal point in this number
should be set to o1-11.
For example, to have the maximum output frequency displayed as “100.00”, set the o1-10 = 1000 and o1-11 = 2 (i.e.,
1000 with 2 decimal points).
No.
<1> U2- and U3- parameters cannot be selected.
<2> Setting range varies by the software version the drive is running. Software versions 6002 or later allow o1-01 to be changed during run.
Software versions 6002 or later: 104 to 903 (U1-04 to U9-03)
Software versions 6001 or earlier: 104 to 621 (U1-04 to U6-21)
Name Setting Range Default
o1-01 Drive Mode Unit Monitor Selection
104 to 903
(U1-04 to U9-03)
<1> <2>
106 (U1-06)
No. Name Setting Range Default
o1-02 User Monitor Selection after Power Up 1 to 5 1
No. Name Setting Range Default
o1-03 Digital Operator Display Selection 0 to 3 0