5.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 159
5.7 H: Terminal Functions
H parameters are used to assign functions to the external terminals.
◆ H1: Multi-Function Digital Inputs
■ H1-01 to H1-06: Functions for Terminals S1 to S6
These parameters assign functions to the multi-function digital inputs. The settings 0 to 7E determine function for each
terminal and are explained below.
Note: If not using an input terminal or if using the through-mode, set that terminal to “F”.
Table 5.16 Digital Multi-Function Input Settings
No.
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Parameter Name
Setting
Range
Default
H1-01 Multi-Function Digital Input S1 Terminal Function Selection 1 to 7E 40 (F): Forward Run Command (2-wire sequence)
H1-02 Multi-Function Digital Input S2 Terminal Function Selection 1 to 7E 41 (F): Reverse Run Command (2-wire sequence)
H1-03 Multi-Function Digital Input S3 Terminal Function Selection 0 to 7E 24: External Fault
H1-04 Multi-Function Digital Input S4 Terminal Function Selection 0 to 7E 14: Fault Reset
H1-05 Multi-Function Digital Input S5 Terminal Function Selection 0 to 7E 3 (0) <1>: Multi-Step Speed Reference 1
H1-06 Multi-Function Digital Input S6 Terminal Function Selection 0 to 7E 4 (3) <1>: Multi-Step Speed Reference 2
Setting
<1> This setting is valid from software versions 6000 or later.
Function Page Setting Function Page
0 3-Wire Sequence 160 20 to 2F External Fault 165
1 LOCAL/REMOTE Selection 160 30 PID Integral Reset 165
2 External Reference 1/2 161 31 PID Integral Hold 165
3 Multi-Step Speed Reference 1
161
34 PID Soft Starter Cancel 165
4 Multi-Step Speed Reference 2 35 PID Input Level Selection 165
5 Multi-Step Speed Reference 3 40 Forward Run/Stop (2-wire sequence)
165
6 Jog Reference Selection 161 41 Reverse Run/Stop (2-wire sequence)
7 Accel/Decel Time 1 161 42 Run/Stop (2-Wire sequence 2)
166
8 Baseblock Command (N.O.)
161
43 FWD/REV (2-Wire sequence 2)
9 Baseblock Command (N.C.) 44 Offset Frequency 1 Addition
166A Accel/Decel Ramp Hold 161 45 Offset Frequency 2 Addition
B Drive Overheat Alarm (oH2) 161 46 Offset Frequency 3 Addition
C Terminal A1/A2 Enable/Disable 162 47 <1> Node Setup 166
F Not used/Through Mode 162 50 Disturb Function Cancel 166
10 Up Command
162
51 Synchronous Accel/Decel 166
11 Down Command 53 Energy Saving On/Off 166
12 Forward Jog
163
59 DC Injection Braking 1 166
13 Reverse Jog 60 DC Injection Braking 2 167
14 Fault Reset 163 61 External Speed Search Command 1 167
15 Fast-Stop (N.O.) 163 62 External Speed Search command 2 167
16 Motor 2 Selection 164 65 KEB 1 (N.C.) 167
17 Fast-stop (N.C.) 163 66 KEB 1 (N.O.)
18 Timer Function Input 164 67 Communications Test Mode 167
19 PID Disable 164 7C Short-Circuit Braking (N.O.)
167
1A Accel/Decel Time Selection 2 164 7D Short-Circuit Braking (N.C.)
1B Program Lockout 164 7E
Forward/Reverse Detection (V/f Control with
Simple PG Feedback)
168