B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 353
◆ o: Operator Related Parameters
o parameters are used to set up the LED digital operator displays.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M
o1: Digital Operator Display Selection
Use o1 parameters to configure the digital operator display.
o1-01
<15>
Drive Mode Unit Monitor
Selection
When the drive is first switched on, the frequency reference
appears on the digital operator screen. Scrolling through
the operator display will show the direction of the motor,
followed by the output frequency, output voltage, and then
the user specified monitor (U1-).
o1-01 selects the content to display the output voltage in
this sequence.
o1-02 selects the monitor to display upon power-up. To
select a different monitor, set 1 to o1-01 where the
desired monitor is expressed as U1-. Note that the
control mode determines which monitors are available.
104 to 903 106 A A A 500
213
Set to U1-06 as a default (Output
Voltage Reference).
NOTE: Setting range varies by the
software version the drive is running.
Software versions 6002 or later allow
this value to be changed during run.
Software versions 6002 or later: 104 to
903
Software versions 6001 or earlier: 104
to 621
o1-02
<15>
User Monitor Selection
after Power Up
Selects the monitor to display upon power-up.
1: Frequency Reference (U1-01)
2: Forward/Reverse
3: Output Frequency (U1-02)
4: Output Current (U1-03)
5: User Monitor (set by o1-01)
1 to 5 1 AAA 501 213
o1-03
Digital Operator Display
Selection
Sets the units to display the frequency reference and output
frequency.
0: Hz
1: % (100% = E1-04)
2: r/min (enter the number of motor poles into E2-04, E4-
04, or E5-04)
3: User defined by parameters o1-10 and o1-11
0 to 3 0 AAA 502 213
o1-10
User-Set Display Units
Maximum Value
These settings define the display values when o1-03 is set
to 3.
o1-10 sets display values when operating at the maximum
output frequency.
o1-11 sets the position of the decimal positions.
1 to 60000
<10> AAA 520 214
o1-11
User-Set Display Units
Decimal Display
0 to 3
<10> AAA 521 214
o2: Digital Operator Keypad Functions
Use o2 parameters to configure LED digital operator key functions.
o2-01
LO/RE Key Function
Selection
Enables/Disables the digital operator LO/RE key.
0: Disabled
1: Enabled
0,1 1 AAA 505 214
o2-02
STOP Key Function
Selection
Enables/Disables the operator panel STOP key when the
drive is operated form external sources (not operator).
0: Disabled
1: Enabled
0,1 1 AAA 506 214
o2-03
User Parameter Default
Va lu e
Allows storing of parameter settings as a User Initialization
Selection (value 1110 for A1-03). The value returns to 0
after entering 1 or 2.
0: No Change
1: Set Defaults - Saves current parameter settings as user
initialization.
2: Clear All - Clears the currently saved user initialization.
0 to 2 0 AAA 507 215
o2-04
<18>
Drive Model Selection
Sets the drive model.
This parameter only needs to be set when installing a new
control board. Do not change for other reason.
0 to FF <11> AAA 508 215
o2-05
Frequency Reference
Setting Method Selection
Selects if the ENTER key must be pressed when inputting
the frequency reference by the operator keypad.
0: Data/Enter key must be pressed to enter a frequency
reference.
1: Data/Enter key is not required. The frequency reference
is adjusted by the UP and DOWN keys.
0, 1 0 AAA 509 215