B.3 Parameter Table
354 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
o2-06
Digital Operator
Disconnection Operation
Sets drive action when the digital operator is removed in
LOCAL mode or with b1-02 = 0.
0: The drive will continue operation
1: The drive will trigger a fault (oPR) and the motor will
coast to stop
0, 1 0 A A A 50A 216
o2-07
<18>
Motor Direction at Power
Up when Using Operator
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to
the digital operator.
0 to 1 0 A A A 527 216
o2-09 Reserved – – – – – – 50D –
o3: Copy Function
Use o3 parameters to Read, Copy and Verify the parameter settings to and from the drive.
o3-01 Copy Function Selection
Selects the copy function operation.
0: No action
1: READ
2: COPY
3: VERIFY
NOTE: When using the copy function, the drive model
number (o2-04) and the software number (U1-14) must
match or an error will occur.
0 to 3 0 A A A 515
216
o3-02 Copy Allowed Selection
Locks the READ operation to prevent accidental
overwriting of the data stored in the LED operator.
0: READ operation prohibited
1: READ operation allowed
0, 1 0 A A A 516
216
o4: Maintenance Monitor Settings
Use o4 parameters to perform maintenance.
o4-01
Cumulative Operation Time
Setting
Sets the value for the cumulative operation time of the
drive in units of 10 h.
0 to 9999 0 A A A 50B 217
o4-02
Cumulative Operation Time
Selection
Determines, how the cumulative operation time (U4-01) is
counted.
0: Logs power-on time
1: Logs operation time when the drive output is active
(output operation time).
0 to 1 0 A A A 50C 217
o4-03
Cooling Fan Operation
Time Setting
Sets the value of the fan operation time monitor U4-03 in
units of 10 h.
<41>
0 to 9999 0 A A A 50E 217
o4-05
Capacitor Maintenance
Setting
Sets the value of the capacitor maintenance time monitor
U4-05.
0 to 150 0% A A A 51D 217
o4-07
DC Bus Pre-charge Relay
Maintenance Setting
Sets the value of the Soft Charge Bypass Relay
Maintenance monitor U4-06.
0 to 150 0% A A A 523 217
o4-09 IGBT Maintenance Setting Sets the value of the IGBT Maintenance monitor U4-07. 0 to 150 0% A A A 525 218
o4-11 U2, U3 Initialization
Selects if U2- (Fault Trace), U3- (Fault History)
monitors are reset at drive initialization.
0: Save the contents of the U2- and U3-
parameters.
1: Reset the contents of the U2- and U3-
parameters.
0 to 1 0 A A A 510 218
o4-12 kWh Monitor Initialization
Selects if U4-10 and U4-11 (kWh monitor) are reset at
drive initialization.
0: Save the contents of U4-10 and U4-11.
1: Reset the contents of U4-10 and U4-11.
0 to 1 0 A A A 512 218
o4-13
Number of Run Commands
Counter Initialization
Selects if the Run command counter (U4-02) is reset at
drive initialization.
0: Save the motor speed monitor (U4-02).
1: Reset the motor speed monitor (U4-02).
0 to 1 0 A A A 528 218
<10> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<11> Default setting is determined by the drive model selection set in parameter o2-04.
<15> Parameter can be changed during run.
<18> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<41> This parameter is valid from software versions 6002 and later. Set in units of 10 hours. Setting o4-03 to 30 will have the start counting the
cooling fan operation time from 300 hours, and U4-03 will display 300H. Earlier software versions set the cooling fan operation time in 1 hour
units.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M