B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 329
◆ d: References
Reference parameters are used to set the various frequency reference values during operation.
No.
<10> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<13> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit.
<15> Parameter can be changed during run.
Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M
d1: Frequency Reference
Use d1 parameters to configure the drive frequency reference.
d1-01
<15>
Frequency Reference 1 Frequency reference
0.00 to
400.00 Hz
<10> <13>
0.00
Hz
SSS 280 143
d1-02
<15>
Frequency Reference 2
Frequency reference when digital input “Multi-Step Speed
Reference 1” (H1- = 3) is on.
0.00
Hz
SSS 281 143
d1-03
<15>
Frequency Reference 3
Frequency reference when digital input “Multi-Step Speed
Reference 2” (H1- = 4) is on.
0.00
Hz
SSS 282 143
d1-04
<15>
Frequency Reference 4
Frequency reference when digital inputs “Multi-Step Speed
Reference 1, 2” (H1- = 3 and 4) are on.
0.00
Hz
SSS 283 143
d1-05
<15>
Frequency Reference 5
Frequency reference when digital input “Multi-Step Speed
Reference 3” (H1- = 5) is on.
0.00
Hz
A A A 284 143
d1-06
<15>
Frequency Reference 6
Frequency reference when digital inputs “Multi-Step Speed
Reference 1, 3” (H1- = 3 and 5) are on.
0.00
Hz
A A A 285 143
d1-07
<15>
Frequency Reference 7
Frequency reference when digital inputs “Multi-Step Speed
Reference 2, 3” (H1- = 4 and 5) are on.
0.00
Hz
A A A 286 143
d1-08
<15>
Frequency Reference 8
Frequency reference when multi-function input “Multi-Step
speed reference 1, 2, 3” (H1- = 3, 4, 5) are on.
0.00
Hz
A A A 287 143
d1-17
<15>
Jog Frequency Reference
Frequency reference when digital inputs “Jog Frequency
Reference”, “Forward Jog” or “Reverse Jog” are on. “Jog
Frequency Reference” has priority over “Multi-Step Speed
Reference 1 to 8”.
6.00
Hz
SSS 292 143
d2: Frequency Upper and Lower Limits
Use d2 parameters to configure the frequency reference limits.
d2-01
Frequency Reference
Upper Limit
Sets the frequency reference upper limit as a percentage of
maximum output frequency (E1-04). Output speed is limited
to this value even if the frequency reference is higher. This
limit applies to all frequency reference sources.
0.0 to
110.0
100.0
%
A A A 289 145
d2-02
<15>
Frequency Reference
Lower Limit
Sets the frequency reference lower limit as a percentage of
maximum output frequency (E1-04). Output speed is limited
to this value even if the frequency reference is lower. This
limit applies to all frequency reference sources.
0.0 to
110.0
0.0% A A A 28A 145
d2-03
<15>
Master Speed Reference
Lower Limit
Sets the minimum frequency reference lower limit if the
frequency reference is input using an analog input. Set as a
percentage of maximum output frequency (E1-04). The
higher of both values d2-02 and d2-03 will be the lower limit.
0.0 to
110.0
0.0% A A A 293 145
d2-04
<15>
Frequency Reference 2
Upper Limit
Sets the frequency reference 2 upper limit as a percentage of
maximum output frequency (E1-04). Output speed is limited
to this value even if the frequency reference 2 is higher. This
limit applies to all frequency reference sources.
0.0 to
110.0
100.0
%
AAA 2A8 145
d2-05
<15>
Frequency Reference 2
Lower Limit
Sets the frequency reference 2 lower limit as a percentage of
maximum output frequency (E1-04). Output speed is limited
to this value even if the frequency reference 2 is lower. This
limit applies to all frequency reference sources.
0.0 to
110.0
0.0% A A A 2A9 146
d7: Offset Frequency
Use d7 parameters to set the offset frequency.
d7-01
<15>
Offset Frequency 1
Added to the frequency reference when the digital input
“Frequency Offset 1” (H1- = 44) is switched on.
-100.0 to
+100.0
0.0% A A A 2B2 146
d7-02
<15>
Offset Frequency 2
Added to the frequency reference when the digital input
“Frequency Offset 2” (H1- = 45) is switched on.
-100.0 to
+100.0
0.0% A A A 2B3 146
d7-03
<15>
Offset Frequency 3
Added to the frequency reference when the digital input
“Frequency Offset 3” (H1- = 46) is switched on.
-100.0 to
+100.0
0.0% A A A 2B4 146