B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 333
Parameter List
B
F: Options
F parameters are used to program the drive for PG feedback and to function with option cards.
E5-24
<18>
Motor Induction
Voltage Constant 2
Set the induced phase-to-phase rms voltage in units of 0.1
mV/(r/min) [mechanical angle].
Set this parameter when using a Yaskawa SMRA Series
SPM Motor.
When setting this parameter, E5-09 should be set to 0. An
alarm will be triggered if both E5-09 and E5-24 are set to
0, or if neither parameter is set to 0.
If E5-03 (Motor Rated Current) is set to 0, however, then
an alarm will not be triggered when both E5-09 and E5-
24 are set to 0.
0.0 to
2000.0
<9> −−S 353 155
<2> Default setting is determine by the control mode set in parameter A1-02. The value shown is for A1-02 = 0-V/f Control.
<9> Default setting is determined by the motor code set to parameter E5-01.
<11> Default setting is determined by the drive model selection set in parameter o2-04.
<14> Upper limit of the setting range is determined by the rated current for motor 2 set to E4-01.
<15> Parameter can be changed during run.
<17> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<18> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<19> Parameter ignored when E1-11, Motor 1 Mid Output Frequency 2, and E1-12, Motor 1 Mid Output Frequency Voltage 2, are set to 0.0.
<20> Setting units vary by the maximum allowable motor capacity, which is determined by C6-01 and o2-04. Drives up to 11 kW display a two-
digit value, while drives 11 kW and larger display a single-digit value.
<23> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller.
<24> If using a Yaskawa SMRA Series SPM Motor, the default setting is 1800 r/min.
<29> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0.
<30> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f Control.
<33> Default setting is determined by the drive model selection set in parameter o2-04 and C6-01, Drive Duty Selection.
<34> The motor rated current must be set higher than the motor no-load current (E2-01 > E2-03).
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M
F1: PG Speed Control Card Settings
Use F1 parameters to set up the drive for V/f Control with Simple PG Feedback. These parameters are enabled only when H6-01 = 03
F1-02 PG 1 Pulses Per Revolution
Sets stopping method when a PG open circuit fault (PGO)
occurs. Refer to parameter F1-14.
0: Ramp to Stop - Decelerate to stop using the active
deceleration time.
1: Coast to Stop
2: Fast-stop - Decelerate to stop using the deceleration time
in C1-09.
3: Alarm only - Drive continues operation.
0 to 3 1 A −− 381 156
F1-03
Operation Selection at
Overspeed (oS)
Sets the stopping method when an overspeed (OS) fault
occurs. Refer to F1-08 and F1-09.
0: Ramp to stop - Decelerate to stop using the active
deceleration time.
1: Coast to stop
2: Fast-stop - Decelerate to stop using the deceleration time
in C1-09.
3: Alarm Only - Drive continues operation.
0 to 3 1 A −− 382 156
F1-04
Operation Selection at
Deviation (dEv)
Sets the stopping method when a speed deviation (DEV)
fault occurs. Refer to F1-10 and F1-11.
0: Ramp to stop - Decelerate to stop using the active
deceleration time.
1: Coast to stop
2: Fast-stop - Decelerate to stop using the deceleration time
in C1-09.
3: Alarm only - Drive continues operation.
0 to 3 3 A −− 383 156
No. Name Description Range Def.
Control
Mode
Addr. Hex Pg.
V/f
OL
V
PM