B.3 Parameter Table
334 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
F1-08 Overspeed Detection Level
Sets the speed feedback level which has to be exceeded for
the time set in F1-09 before an OS fault will occur.
Set as a percentage of the maximum output frequency (E1-
04).
0 to 120 115% A −− 387 156
F1-09
Overspeed Detection Delay
Time
Sets the time in seconds for which the speed feedback has
to exceed the overspeed detection level F1-08 before an OS
fault will occur.
0.0 to 2.0 1.0 A −− 388 156
F1-10
Excessive Speed Deviation
Detection Level
Sets the allowable deviation between motor speed and
frequency reference before a speed deviation fault (DEv) is
triggered.
Set as a percentage of the maximum output frequency (E1-
04).
0 to 50 10% A −− 389 157
F1-11
Excessive Speed Deviation
Detection Delay Time
Sets the time in seconds for which a deviation between
motor speed and frequency reference has to exceed the
speed deviation detection level F1-10 before a DEV fault
will occur.
0.0 to
10.0
0.5 s A −− 38A 157
F1-14
PG Open-Circuit Detection
Time
Sets the time for which no PG pulses must be detected
before a PG Open (PGO) fault is triggered.
0.0 to
10.0
2.0 s A −− 38D 157
F6: Communication Option Card
Use F6 parameters to program the drive for serial communication.
F6-01
Communications Error
operation Selection
Selects the operation after a communications error
occurred.
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast-stop using C1-09
3: Alarm only
0 to 3 1 A A A 3A2 157
F6-02
External Fault from Comm.
Option Detection Selection
Sets when an external fault from a comm option is
detected.
0: Always detected
1: Detection during Run only
0 or 1 0 A A A 3A3 157
F6-03
External Fault from Comm.
Option Operation Selection
Selects the operation after an external fault set by a
communications option (EF0).
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast-stop using C1-09
3: Alarm only
0 to 3 1 A A A 3A4 157
F6-07
NetRef/ComRef Function
Preselection Capability
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
0, 1 1 A A A 3A8 158
F6-08
<18>
Comm. Parameter Reset
0: Communication-related parameters (F6-) are not
reset when the drive is initialized using A1-03.
1: Reset all communication-related parameters (F6-)
when the drive is initialized using A1-03.
0 to 1 0 A A A 36A 158
F6-10 CC-Link Node Address Sets the node address if a CC-Link is installed. 0 to 64 0 A A A 3E6 –
F6-11
CC-Link Communication
Speed
0: 156 kbps
1: 625 kbps
2: 2.5 kbps
3: 5 Mbps
4: 10 Mbps
0 to 4 0 AAA 3E7 –
F6-14 bUS Error Auto Reset
Selects if a BUS fault can be automatically reset.
0: Disabled
1: Enabled
0 or 1 0 A A A 3BB –
F6-30
PROFIBUS-DP Node
Address
Sets the node address for a PROFIBUS. 0 to 125 0 A A A 3CB –
F6-31
PROFIBUS-DP Clear Mode
Selection
Selects the operation when a "Clear Mode" command is
received.
0: Resets drive operation.
1: Maintains the previous operation state.
0 or 1 0 A A A 3CC –
F6-32
PROFIBUS-DP Data
Format Selection
0: PPO Type
1: Conventional
0 or 1 0 A A A 3CD –
No. Name Description Range Def.