5.10 o: Operator Related Settings
214 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Note: 1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
x U1-01: frequency reference
x U1-02: output frequency
x U1-05: motor speed
x U1-16: output frequency after softstarter (accel/decel ramp generator)
x d1-01 to d1-17: frequency references
2. Setting o1-03 to 2 requires that the number of motor poles be entered to E2-04, E4-04, and E5-04.
o1-10: User-Set Display Units Maximum Value
Determines the display value that is equal to the maximum output frequency. The decimal number is defined by
parameter o1-11.
Note: This setting changes automatically when o1-03 is changed. o1-10 can only be adjusted when o1-03 is set to 3.
o1-11: User-Set Display Units Decimal Display
Determines the number of digits for user-set display if o1-03 is set to 3. The setting value is equal to the number of
decimal places. The maximum display value is defined by o1-10.
Note: This setting changes automatically when o1-03 is changed. o1-11 can only be adjusted when o1-03 is set to 3.
o2: Digital Operator Keypad Functions
These parameters determine the functions assigned to the operator keys.
o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
Parameter o2-01 determines whether the LO/RE key on the digital operator will be enabled or not for switching between
LOCAL and REMOTE.
Setting 0: Disabled
The LO/RE key is disabled.
Setting 1: Enabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL
is selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating
machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode.
o2-02: STOP Key Function Selection
Selects if the STOP key on the digital operator can be used to stop the operation when the drive is controlled from a
remote source (i.e., not from digital operator).
Setting 0: Disabled
The STOP key has no function when the drive is controlled by a source other than the digital operator. The drive can only
be stopped from the Run command source that has been selected.
No. Name Setting Range Default
o1-10 User-Set Display Units Maximum Value 1 to 60000
Determined by
o1-03
No. Name Setting Range Default
o1-11 User-Set Display Units Decimal Display 0 to 3
Determined by
o1-03
No. Name Setting Range Default
o2-01 LO/RE Key Function Selection 0 or 1 1
No. Name Setting Range Default
o2-02 STOP Key Function Selection 0 or 1 1