2.2 Mechanical Installation
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 35
Mechanical
Installation
2
Note: 1. When installing drives of different heights in the same enclosure panel, the tops of the drives should line up. Leave space between the
top and bottom of stacked drives for cooling fan replacement if required. Using this method, it is possible to replace the cooling fans
later.
2. Do not install T1000V finless drive using the Side-by-Side method available in T1000V heatsink-cooled drive. Improper drive
cooling may result in damage to the drive. Install T1000V finless drive with a minimum side-by-side clearance of 30 mm (1.18 in).
Exterior and Mounting Dimensions
Table 2.2 Drive Models and Types
Note: Refer to Specifications on page 307 for information on the amount of heat generated by the drive and appropriate cooling
methods.
Protective Design
Drive Model CIMR-TC
Page
Single-Phase
200 V Class
Three-Phase
200 V Class
Three-Phase
400 V Class
IP20/Heatsink-Cooled
Drive
BV0001B
BV0002B
BV0003B
2V0001B
2V0002B
2V0004B
2V0006B
36
BV0006B
BV0010B
BV0012B
2V0010B
2V0012B
2V0020B
4V0001B
4V0002B
4V0004B
4V0005B
4V0007B
4V0009B
4V0011B
36
IP00/Heatsink-Cooled
Drive
2V0030A
2V0040A
2V0056A
2V0069A
4V0018A
4V0023A
4V0031A
4V0038A
37
IP20/Finless Drive
BV0001J
BV0002J
BV0003J
2V0001J
2V0002J
2V0004J
2V0006J
37
BV0006J
BV0010J
2V0010J
2V0012J
4V0001J
4V0002J
4V0004J
4V0005J
4V0007J
4V0009J
38
BV0012J 2V0020J 4V0011J 38
2V0030J
2V0040J
2V0056J
4V0018J
4V0023J
4V0031J
4V0038J
39
IP00/Finless Drive 2V0069L 39

Table of Contents

Related product manuals