B.3 Parameter Table
352 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
n8-74
<38>
Id No Load Start
Sets Id current level 1 for light loads.
Note: An Operator Programming Error (oPE) occurs if the
setting value deviates from the following condition: n8-
74n8-75n8-50.
0.0 to
250.0%
30.0% −−A5C3211
n8-75
<38>
Id No Load End
Sets Id current level 2 for light loads.
Note: An Operator Programming Error (oPE) occurs if the
setting value deviates from the following condition: n8-
74n8-75n8-50.
<46> 50.0% −−A5C4211
n8-76
<38>
Id Filter Time Sets Id filter time for PM OLV control mode.
0 to 5000
ms
200
ms
−−A5CD211
n8-77
<38>
Id Load Slp End Sets Id current level for high loads. <47> 90.0% −−A5CE211
n8-78
<38>
Id Medium Value Sets Id current level for medium loads.
-200.0 to
200.0%
0.0% −−A5F4211
n8-87
<38>
Output Voltage Limit
Selection
Sets how the output voltage limit should be used. 0,1 0 −−A2BC211
n8-88
<38>
Output Voltage Limit
Switch Current Level
Sets the current level to switch the output voltage limit
sequence. Set as a percentage of the motor rated current
(E5-03).
0 to 400% 400% −−A2BD211
n8-89
<38>
Output Voltage Limit
Switch Hysteresis Width
Sets hysteresis used for the current level that switches the
output voltage limit sequence. Set as a percentage of the
motor rated current (E5-03).
0 to n8-88 3% −−A2BE211
n8-90
<38>
Output Voltage Limit
Switch Speed
Sets the speed level for switching the output voltage limit
sequence. Set as a percentage of the maximum output
frequency (E1-04).
0 to 200% 200% −−A2BF211
n8-91
<38>
Output Voltage Limit ld
Limit
Sets the limit value for the ld operation of the feedback type
output voltage limitation. This setting is available only at
n8-87 = 0.
0 to -
200%
-50% −−A2F7212
n9: Hardware Settings
Using these parameters, drive output voltage can be adjusted.
n9-10 AVR Time Constant Sets a delay time for output voltage compensation.
0.0 to
100.0
1.0
ms
AAA SD9 210
n9-12
On-Delay Compensation
Time
Sets the time value used for IGBT On-delay compensation.
0.00 to
20.00
<11> AAA SDB 210
n9-62
On-Delay Compensation
Derating Start Frequency
Sets the frequency at which the drive begins to compensate
the output voltage for the IGBT On-Delay.
0.0 to
[E1-04]
Hz
0.0
Hz
AAA 64F 210
n9-63
On-Delay Compensation
Disable Frequency
Sets the frequency at which the drive stops compensating
the output voltage for the IGBT On-Delay.
0.0 to
[E1-04]
Hz
0.0
Hz
AAA 650 210
<9> Default setting is determined by the motor code set to parameter E5-01.
<11> Default setting is determined by the drive model selection set in parameter o2-04.
<15> Parameter can be changed during run.
<17> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<38> This parameter is valid from software version 6002 or later. This setting rarely needs to be changed from its default value.
<39> Setting range varies by the software version the drive is running. Software versions 6002 or later allow this value to be changed during run.
Software versions 6002 or later: 0%, 20 to 200%
Software versions 6001 or earlier: 20 to 200%
<40> Setting range varies by the software version the drive is running. Software versions 6002 or later allow this value to be changed during run.
Software versions 6002 or later: -200.0 to 200.0%
Software versions 6001 or earlier: -200.0 to 0.0%
<46> Setting range is determined as follows: (n8-74 + 0.1%) to (n8-50 - 0.1%).
<47> Setting range is determined as follows: (n8-50 + 0.1%) to 250.0%.