5.9 n: Special Adjustments
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 211
Parameter Details
5
n8-76: Id Filter Time (for PM OLV)
Sets Id filter time for PM OLV control mode.
Note: This parameter is valid from software version 6002 or later.
n8-77: Id Load Slp End (for PM OLV)
Sets Id current level for high loads.
Note: This parameter is valid from software version 6002 or later.
n8-78: Id Medium Value (for PM OLV)
Sets Id current level for medium loads.
Note: This parameter is valid from software version 6002 or later.
n8-87: Output Voltage Limit Selection
Sets how the output voltage limit should be used. This setting is rarely needs to be changed.
Note: This parameter is valid from software version 6002 or later.
0: Feedback type
1: Feed Forward type
n8-88: Output Voltage Limit Switch Current Level
Sets the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03).
This setting is rarely needs to be changed.
Note: This parameter is valid from software version 6002 or later.
n8-89: Output Voltage Limit Switch Hysteresis Width
Sets hysteresis used for the current level that switches the output voltage limit sequence. Set as a percentage of the motor
rated current (E5-03). This setting is rarely needs to be changed.
Note: This parameter is valid from software version 6002 or later.
n8-90: Output Voltage Limit Switch Speed
Sets the speed level for switching the output voltage limit sequence. Set as a percentage of the maximum output
frequency (E1-04). This setting is rarely needs to be changed.
Note: This parameter is valid from software version 6002 or later.
No. Name Setting Range Default
n8-76 Id Filter Time 0 to 5000 ms 200 ms
No.
<1> Setting range is determined as follows: (n8-50 + 0.1%) to 250.0%.
Name Setting Range Default
n8-77 Id Load Slp End <1> 90.0%
No. Name Setting Range Default
n8-78 Id Medium Value -200.0 to 200.0% 0.0%
No. Name Setting Range Default
n8-87 Output Voltage Limit Selection 0, 1 0
No. Name Setting Range Default
n8-88 Output Voltage Limit Switch Current Level 0 to 400% 400%
No. Name Setting Range Default
n8-89 Output Voltage Limit Switch Hysteresis Width 0 to n8-88 3%
No. Name Setting Range Default
n8-90 Output Voltage Limit Switch Speed 0 to 200% 200%