B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 337
14 Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is
removed.
OOO163
15 Fast-Stop (N.O.)
Closed: Decelerates at the Fast-Stop time C1-09.
To restart the Fast-Stop input must be released and Run must be cycled.
OOO163
16 Motor 2 Selection
Open: Motor 1 (E1-, E2-)
Closed: Motor 2 (E3-, E4-)
OO–164
17 Fast-stop (N.C.) Open: Decelerates according to C1-09 (Fast-stop Time) O O O 163
18 Timer Function Input
Set the timer delay using parameters b4-01 and b4-02.
Ensure this function is set in conjunction with the multi-function output
timer (H2- = 12).
OOO164
19 PID Disable Closed: PID control disabled O O O 164
1A Accel/Decel Time Selection 2 Switches Accel/Decel times. O O O 164
1B Program Lockout
Open: Parameters can not be edited. (except U1-01 if reference source is
set for operator)
Closed: Parameters may be edited and saved.
OOO164
20 to 2F External Fault
20: N.O., Always Detected, Ramp To Stop
21: N.C., Always Detected, Ramp To Stop
22: N.O., During Run, Ramp To Stop
23: N.C., During Run, Ramp To Stop
24: N.O., Always Detected, Coast To Stop
25: N.C., Always Detected, Coast To Stop
26: N.O., During Run, Coast To Stop
27: N.C., During Run, Coast To Stop
28: N.O., Always Detected, Fast-stop
29: N.C., Always Detected, Fast-stop
2A: N.O., During Run, Fast-stop
2B: N.C., During Run, Fast-stop
2C: N.O., Always Detected, Alarm Only (continue running)
2D: N.C., Always Detected, Alarm Only (continue running)
2E: N.O., During Run, Alarm Only (continue running)
2F: N.C., During Run, Alarm Only (continue running)
OOO165
30 PID Integral Reset Closed: Resets the PID control integral value. O O O 165
31 PID Integral Hold Closed: Maintains the current PID control integral value. O O O 165
34 PID Soft Starter Closed: Disables the PID soft starter b5-17. O O O 165
35 PID Input Switch Closed: Inverses the PID input signal O O O 165
40
Forward Run Command (2-Wire
sequence)
Open: Stop
Closed: Forward run
Note: Can not be set together with Settings 42 or 43.
OOO165
41
Reverse Run Command (2-Wire
sequence)
Open: Stop
Closed: Reverse run
Note: Can not be set together with Settings 42 or 43.
OOO
165
4
2 Run Command (2-Wire sequence 2)
Open: S
top
Closed: Run
Note: Can not be set together with Settings 40 or 41.
OOO166
43
FWD/REV Command (2-Wire
sequence 2)
Open: Forward
Closed: Reverse
Note: Can not be set together with Settings 40 or 41.
OOO166
44 Offset Frequency 1 Addition Closed: Adds d7-01 to the frequency reference. O O O 166
45 Offset Frequency 2 Addition Closed: Adds d7-02 to the frequency reference. O O O 166
46 Offset Frequency 3 Addition Closed: Adds d7-03 to the frequency reference. O O O 166
47
<37> Node Setup Closed: Set up the node address. O O O 166
50 Disturb Function Cancel
Open: Disturb function output is active.
Closed: Cancels the Disturb function.
OOO166
51 Synchronous Accel/Decel
Closed: Assigns the same accel/decel times to all motors in the line so
that they reach the desired frequency at the same time.
OOO166
53 Energy Saving On/Off Closed: Enables the Energy Saving function. O O × 166
59 DC Injection Braking 1 Command Closed: Triggers DC Injection Braking 1 (b2-02) O O × 166
H1 Multi-Function Digital Inputs Settings
H1-
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
PM