B.3 Parameter Table
338 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
60 DC Injection Braking 2 Command Closed: Triggers DC Injection Braking 2 (b2-10) O O 167
61 External Speed Search Command 1
Closed: Activates Current Detection Speed Search from the max. output
frequency (E1-04) if b3-01 = 0. Activates Speed Estimation Type Speed
search if b3-01 =1.
OOO167
62 External Speed Search Command 2
Closed: Activates Current Detection Speed Search from the frequency
reference.
OOO167
65 KEB 1 (N.C.)
Open: KEB 1 enabled
Closed: Normal operation
OOO167
66 KEB 1 (N.O.)
Open: Normal operation
Closed: KEB 1 enabled
OOO167
67 Communications Test Mode Tests the MEMOBUS/Modbus RS-485/422 interface. O 167
7C Short-Circuit Braking (N.O.)
Open: Normal operation
Closed: Short-Circuit Braking
O–O167
7D Short-Circuit Braking (N.C.)
Open: Short-Circuit Braking
Closed: Normal operation
O–O167
7E Forward/Reverse Detection Direction of rotation detection (for V/f with Simple PG Feedback) O O O 168
<37> This setting is valid from software versions 6000 or later.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M
H2: Multi-Function Digital Outputs
Use H2 parameters to assign functions to the multi-function digital outputs.
H2-01
Terminal MA, MB and MC Function
Selection (relay)
Refer to H2 Multi-Function Digital Output
Settings on page 338 for a description of
setting values.
0 to 152
<26>
<26> The availability of certain functions depends on the control method used.
E AAA 40B 168
H2-02
Terminal P1-C1 Function Selection (open-
collector)
0 AAA 40C 168
H2-03
Terminal P2-C2 Function Selection (open-
collector)
2 AAA 40D 168
H2-06 Watt Hour Output Unit Selection
Determines the unit for the watt hour output
signal (H2- = 39). If a digital output is
set to this function, a 200 ms pulse signal is
output when the what hour counter increases
according to the unit selected. Intended to
drive a counter, meter or PLC for logging
kWh.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
0 to 4 0 AAA 437 177
H2 Multi-Function Digital Outputs Settings
H2-
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
P
M
0 During Run Closed: A Run command is active or voltage is output. O O O 168
1 Zero Speed Closed: Output frequency is 0. O O O 169
2 Speed Agree 1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
OOO169
3 User Set Speed Agree 1
Closed: Output frequency and speed reference equal the value in L4-01 (plus or
minus the hysteresis of L4-02).
OOO169
H1 Multi-Function Digital Inputs Settings
H1-
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
PM