B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 339
Parameter List
B
4 Frequency Detection 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
OOO170
5 Frequency Detection 2
Closed: Output frequency is greater than or equal to the value in L4-01, with
hysteresis determined by L4-02.
OOO170
6 Drive Ready
Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive
mode.
OOO171
7 DC Bus Undervoltage Closed: DC bus voltage is below the Uv trip level set in L2-05. O O O 171
8 During Baseblock (N.O.) Closed: There is no output voltage O O O 171
9 Frequency Reference Source
Open: External Reference 1 or 2 supplies the frequency reference
Closed: Digital operator supplies the frequency reference.
OOO171
A Run Command Source
Open: External Reference 1 or 2 supplies the Run command
Closed: Digital operator supplies the Run command.
OOO171
B Torque Detection 1 (N.O.)
Closed: Output current/torque exceeds the torque value set in parameter L6-02 for
longer than the time set in parameter L6-03.
OOO172
C Frequency Reference Loss Closed: Loss of the analog frequency reference detected. Enabled when L4-05 = 1. O O O 172
D Braking Resistor Fault
Closed: Braking resistor or transistor is overheated or faulted out. This selection
requires that braking resistor protection parameter be set for ERF (L8-01 = “1”).
OOO172
E Fault Closed: Fault occurred (other than CPF00 and CPF01). O O O 172
F Not used/Through Mode
Set this value when the terminal is not used, or when using the terminal in the pass-
through mode.
OOO172
10 Minor Fault Closed: An alarm is triggered. O O O 172
11 Reset Command Active Closed: Reset command to the drive is active. O O O 172
12 Timer Output
Timer output, controlled by b4-01 and b4-02. Used in conjunction with the digital
input (H1- = 18 “timer function”).
OOO172
13 Speed Agree 2 Closed: When drive output frequency equals the frequency reference +/- L4-04. O O O 172
14 User Set Speed Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 (plus or
minus L4-04).
OOO173
15 Frequency Detection 3
Closed: When the drive output frequency is less than or equal to the value in L4-03
with the hysteresis determined by L4-04.
OOO173
16 Frequency Detection 4
Closed: When the output frequency is greater than or equal to the value in L4-03
with the hysteresis determined by L4-04.
OOO174
17 Torque Detection 1 (N.C.)
Open: When the output current/torque exceeds the value set in parameter L6-02 for
more time than is set in parameter L6-03.
OOO172
18 Torque Detection 2 (N.O.)
Closed: When
the output current/torque exceeds the
value set in parameter L6-05
for more time than is set in parameter L6-06.
OOO172
19 Torque Detection 2 (N.C.)
Open: Output current/torque exceeds the value set in parameter L6-05 for more
time than is set in parameter L6-06.
OOO172
1A Reverse Direction Closed: Drive is running in the reverse direction. O O O 175
1B During Baseblock (N.C.) Open: Drive is in Baseblock condition. Output is disabled. O O O 175
1C Motor 2 Selection Closed: Motor 2 is selected by a digital input (H1- = 16) O O 175
1E Restart Enabled Closed: An automatic restart is performed O O O 175
1F Overload Alarm oL1 Closed: oL1 is at 90% of its trip point or greater. O O O 175
20 oH Pre alarm Closed: Heatsink temperature exceeds the parameter L8-02 value. O O O 175
30 During Torque Limit Closed: When the torque limit has been reached. O 175
37 During Frequency Output
Closed: Frequency is output
Open: Operation stopped, Baseblock, DC Injection Braking, or Initial Excitation is
being performed.
OOO175
39 Watt Hour Pulse Output
Output units are determined by H2-06, outputs 200 ms pulse for each incremented
kWh count.
OOO176
3C LOCAL/REMOTE Status
Closed: LOCAL
Open: REMOTE
OOO176
3D Speed Search Closed: Speed search is being executed. O O O 176
3E PID Feedback Loss Low
Closed: PID Feedback Loss Low.
PID feedback value is below the level set to b5-13 for longer than the time set in b5-
14.
OOO176
H2 Multi-Function Digital Outputs Settings
H2-
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
P
M