B.3 Parameter Table
340 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
3F PID Feedback Loss High
Closed: PID Feedback Loss High.
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-
37.
OOO176
4A KEB Operation Closed: KEB is being performed. O O O 176
4B Short-Circuit Brake Closed: Short-Circuit Braking is active. O O 176
4C During Fast-stop Closed: Fast-stop command is entered O O O 176
50 Disturb increase
Closed: Disturb waveform acceleration
Open: Disturb waveform deceleration
OOO176
51 During Disturb output
Closed: Disturb waveform is active
Open: Disturb waveform is not being output
OOO176
52 Uv during KEB Closed: DC bus voltage has fallen below L2-05 during KEB O O O 177
100 to 10D
Reserved Output Switching
of 0 to D
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1 to reverse the output signal of that specific function.
OOO
177
10F to 11B
Reserved Output Switching
of F to 1B
OOO
11E to 120
Reserved Output Switching
of 1E to 20
OOO
137, 138
Reserved Output Switching
of 37 and 38
OOO
13C to 13E
Reserved Output Switching
of 3C to 3E
OOO
14A
Reserved Output Switching
of 4A
××O
14B, 14C
Reserved Output Switching
of 4B and 4C
OOO
14F
Reserved Output Switching
of 4F
OOO
150, 151
Reserved Output Switching
of 50 and 51
O ××
152
Reserved Output Switching
of 52
OOO
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M
H3: Multi-Function Analog Inputs
Use H3 parameters to set the multi-function analog input terminals.
H3-01
Terminal A1 Signal Level
Selection
Sets the input level for terminal A1.
0: 0 to +10 V (lower limit)
1: 0 to +10 V (no lower limit)
0, 1 0 A A A 410 177
H3-02
Terminal A1 Function
Selection
Sets the function of terminal A1.
When terminal A1 is not used or is used as a through
terminal, this parameter must be set to “F”.
0 to 1F
<26>
0 A A A 434 178
H3-03
<15>
Terminal A1 Gain Setting
Sets the level of the input value selected in H3-02 when 10
V is input at terminal A1.
-999.9 to
999.9
100.0
%
AAA 411 178
H3-04
<15>
Terminal A1 Bias Setting
Sets the level of the input value selected in H3-02 when 0
V is input at terminal A1.
-999.9 to
999.9
0.0% A A A 412 178
H3-09
Terminal A2 Signal Level
Selection
Sets the input signal level for terminal A2.
0: 0 to +10 V (with lower limit)
1: 0 to +10 V (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3 2 A A A 417 179
Switch between current or voltage inputs by
using DIP switch S1-2 switch on the terminal
board.
H3-10
Terminal A2 Function
Selection
Sets the function of terminal A2.
When terminal A2 is not used or is used as a through
terminal, this parameter must be set to “F”.
0 to 1F
<26>
0 A A A 418 180
H2 Multi-Function Digital Outputs Settings
H2-
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
P
M

Table of Contents