EasyManua.ls Logo

YASKAWA T1000V - Page 180

YASKAWA T1000V
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.7 H: Terminal Functions
180 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Setting 1: 0 to 10 Vdc without Lower Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted. Refer to the explanation of H3-01, Setting 1. Refer
to Setting 1: 0 to 10 Vdc without Limit on page 178
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2. Refer to Multi-Function Analog Input Terminal Settings
on page 180 for a list of functions and descriptions.
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the selected input value that is equal to 10 Vdc/20 mA input at terminal A2 (Gain).
Parameter H3-12 sets the level of the selected input value that is equal to 0 Vdc/4 mA/0 mA input at terminal A2.
Both can be used to adjust the analog input A2 characteristics. The setting works in the same way as parameters H3-03
and H3-04 for analog input A1.
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to both analog inputs A1 and A2.
An analog input filter can be used to prevent erratic drive control when a “noisy” analog reference is used. The drive
operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing
analog signals.
Multi-Function Analog Input Terminal Settings
This section describes the various functions that can be assigned to terminal A1 and A2 by setting H3-02 and H3-10.
Note: The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values
when selecting and adjusting analog input functions.
No. Name Setting Range Default
H3-10 Terminal A2 Function Selection 0 to 1F 0
No. Name Setting Range Default
H3-11 Terminal A2 Gain Setting -999.9 to 999.9% 100.0%
H3-12 Terminal A2 Bias Setting -999.9 to 999.9% 0.0%
No. Name Setting Range Default
H3-13 Analog Input Filter Time Constant 0.00 to 2.00 s 0.03 s
Setting Function Page Setting Function Page
0 Frequency Bias 181 F Not used/Through Mode 181
1 Frequency Gain 181 10 Forward Torque Limit
181
2 Auxiliary Frequency Reference 181 11 Reverse Torque Limit
4 Output Voltage Bias 181 12 Regenerative Torque Limit
7 Overtorque/Undertorque Detection Level 181 15 General Torque Limit
B PID Feedback 181 16 Differential PID Feedback 182
C PID Set Point 181 1F Not used/Through Mode 181
E Motor Temperature (PTC input) 181

Table of Contents

Related product manuals