EasyManua.ls Logo

YASKAWA T1000V - Page 170

YASKAWA T1000V
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.7 H: Terminal Functions
170 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Note: The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
Figure 5. 47
Figure 5.47 User Set Speed Agree 1 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 195 for details on setting the
detection width.
Setting 4: Frequency Detection 1
Output is closed as long as the output frequency is below the detection level set in L4-01 plus the hysteresis set in L4-02.
It closes when the output frequency falls below L4-01.
Note: The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
Figure 5. 48
Figure 5.48 Frequency Detection 1 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 195 for details on setting the
detection width.
Setting 5: Frequency Detection 2
Output closes whenever the output frequency is equal to or above the detection level set in L4-01. The output opens when
the output frequency falls below L4-01 minus the hysteresis set in L4-02.
Note: The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
Status Description
Open Output frequency or frequency reference are outside the range of L4-01 ± L4-02.
Closed Output frequency and the frequency reference are both with in the range of L4-01 ± L4-02.
Status Description
Open Output frequency exceeded L4-01 + L4-02.
Closed Output frequency is below L4-01 or has not exceeded L4-01 + L4-02.
Status Description
Open Output frequency is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed Output frequency exceeded L4-01.
Output
frequency
User Set
Speed Agree 1
OFF
ON
Frequency
reference
OFF
ON
Frequency
reference
Output
frequency
L4-01
+/- L4-02
L4-01
+/- L4-02
Output
frequency
L4-02
Frequency
detection 1
ON
OFF
L4-02
L4-01
L4-01

Table of Contents