5.7 H: Terminal Functions
174 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Figure 5. 52
Figure 5.52 Frequency Detection 3 Example with Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/–) on page 195 for details on setting
the detection width.
Setting 16: Frequency Detection 4
Output closes whenever the output frequency is equal to or above the detection level set in L4-03. The output opens when
the output frequency falls below L4-03 minus the hysteresis set in L4-04. As the detection level L4-03 is a signed value,
the detection works in the specified direction only.
Figure 5. 53
Figure 5.53 Frequency Detection 4 Example with Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/–) on page 195 for details on setting
the detection width.
Status Description
Open Output frequency is below L4-03 minus L4-04 or has not exceeded L4-03 yet.
Closed Output frequency exceeded L4-03.
Output
frequency
L4-04
Frequency
detection 3
ON
OFF
L4-03
Output
frequency
L4-04
Frequency
Detection 4
ON
OFF
L4-03