5.1 A: Initialization
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 103
Setting 2: Open Loop Vector
• For general, variable-speed applications.
• For applications requiring precise speed control, quick response, and higher torque at low speeds.
Setting 5: PM Open Loop Vector
For operating SPM, IPM, and various permanent magnet motors. Takes advantage of Energy Saving features when
operating with derated torque.
■
A1-03: Initialize Parameters
Resets parameter settings back to their original default values. After the initialization the parameter automatically returns
to 0.
Setting 0: No Initialize
Setting 1110: User Initialize
The modified drive parameters are returned to the values selected as user settings. User settings are stored when
parameter o2-03 = “1: Set Defaults”.
Note: A “user-initialization” resets all parameters to a user-defined set of default values that were previously saved to the drive. To
clear the user-defined default values, set parameter o2-03 to “2”.
Setting 2220: 2-Wire Initialization
Resets all parameters back to their original default settings with digital inputs S1 and S2 configured as forward run and
reverse run, respectively. A 2-wire sequence assigns functions to input terminals S1 and S2. Refer to page 181 for more
information.
Setting 3330: 3-Wire Initialization
The drive parameters are returned to factory default values with digital inputs S1, S2, and S5 configured as run, stop, and
forward/reverse respectively. A 3-wire sequence assigns functions to terminals S1, S2, and S5. Refer to page 175 for
more information.
Setting 5550: oPE04 Reset
If parameters on a certain drive have been edited and then a different terminal block is installed with different settings
saved in its built-in memory, an oPE04 error will appear on the display. To use the parameter settings saved to the
terminal block memory, set A1-02 to “5550”.
Notes on Parameter Initialization
The parameters shown in Table 5.1 will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. The
fault history will not be reset when the drive is initialized by A1-03 = 2220 or 3330. The control mode in A1-02 is not
reset when A1-03 is set to 2220 or 3330.
Table 5.1 Parameters not Changed by Drive Initialization
No. Parameter Name Setting Range Default
A1-03 Initialize Parameters 0, 1110, 2220, 3330, 5550 0
No. Parameter Name
A1-00 Language Selection
A1-02 Control Method Selection
E5-01 PM Motor Code Selection
E5-02 Motor Rated Capacity (for PM motors)
E5-03 Motor Rated Current (for PM motors)
E5-04 Motor Poles (for PM motors)
E5-05 Motor Armature Resistance (for PM motors)
E5-06 Motor d Axis Inductance (for PM motors)
E5-07 Motor q Axis Inductance (for PM motors)
E5-09 Motor Induction Voltage Constant 1 (for PM motors)
E5-24 Motor Induction Voltage Constant 2 (for PM motors)
o2-04 Drive/kVA Selection
L8-35 Installation Selection