5.2 b: Application
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 125
Parameter Details
5
b5-05: Derivative Time (D)
Sets the time the drive predicts the PID input/PID feedback signal based on the derivative of the PID input/PID feedback.
Longer time settings will improve the response but can cause vibrations. Shorter settings will reduce the overshoot but
also reduce the controller responsiveness. D control is disabled by setting b5-05 to zero seconds.
b5-06: PID Output Limit
Sets the maximum output possible from the entire PID controller. Set as a percentage of the maximum frequency (E1-
04).
b5-07: PID Offset Adjustment
Sets the offset added to the PID controller output. Set as a percentage of the maximum frequency.
b5-08: PID Primary Delay Time Constant
Sets the time constant for the filter applied to the output of the PID controller. Normally, change is not required.
Note: Effective in preventing oscillation when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the
cycle of the resonant frequency. Increasing this time constant reduces the responsiveness of the drive.
b5-09: PID Output Level Selection
Normally, the output of the PID function increase whenever the PID input is negative (feedback below setpoint). Using
b5-09 the PID controller can be set up for applications that require opposite operation.
Setting 0: Normal Output
A negative PID input causes an increase in the PID output (direct acting).
Setting 1: Reverse Output
A negative PID input causes a decrease in the PID output (reverse acting).
b5-10: PID Output Gain Setting
Applies a gain to the PID output and can be helpful when the PID function is used to trim the frequency reference (b5-01
= 3 or 4). Increasing b5-10 causes the PID function to have a greater regulating effect on the frequency reference.
No. Name Setting Range Default
b5-05 Derivative Time (D) 0.00 to 10.00 s 0.00 s
No. Name Setting Range Default
b5-06 PID Output Limit 0.0 to 100.0% 100.0%
No. Name Setting Range Default
b5-07 PID Offset Adjustment -100.0 to 100.0% 0.0%
No. Name Setting Range Default
b5-08 PID Primary Delay Time Constant 0.00 to 10.00 s 0.00 s
No. Parameter Name Setting Range Default
b5-09 PID Output Level Selection 0 or 1 0
No. Name Setting Range Default
b5-10 PID Output Gain Setting 0.00 to 25.00 1.00