5.5 E: Motor Parameters
150 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
■ E2-07: Motor Iron-Core Saturation Coefficient 1
This parameter sets the motor iron saturation coefficient at 50% of the magnetic flux. If Rotational Auto-Tuning
completes successfully, then this value is automatically calculated.
■
E2-08: Motor Iron-Core Saturation Coefficient 2
This parameter sets the motor iron saturation coefficient at 75% of the magnetic flux. If Rotational Auto-Tuning
completes successfully, then this value is automatically calculated.
■
E2-09: Motor Mechanical Loss
This parameter sets to the motor mechanical loss as a percentage of motor rated power (kW) capacity.
Adjust this setting when there is a large amount of torque loss due to motor bearing friction.
The setting for the mechanical loss is added to the torque.
■
E2-10: Motor Iron Loss for Torque Compensation
This parameter sets the motor iron loss in watts.
■
E2-11: Motor Rated Power
This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If
Auto-Tuning completes successfully, the value entered will automatically be saved to E2-11.
■
E2-12: Motor Iron-Core Saturation Coefficient 3
This parameter sets the motor iron saturation coefficient at 130% of the magnetic flux.
No. Parameter Name Setting Range Default
E2-07 Motor Iron-Core Saturation Coefficient 1 0.00 to 0.50 0.50
No. Parameter Name Setting Range Default
E2-08 Motor Iron-Core Saturation Coefficient 2 E2-07 to 0.75 0.75
No. Parameter Name Setting Range Default
E2-09 Motor Mechanical Loss 0.0 to 10.0% 0.0%
No. Parameter Name Setting Range Default
E2-10 Motor Iron Loss for Torque Compensation 0 to 65535 W
Determined by
C6-01 and o2-04
No. Parameter Name Setting Range Default
E2-11 Motor Rated Power 0.00 to 650.00 kW
Determined by
C6-01 and o2-04
No. Parameter Name Setting Range Default
E2-12 Motor Iron-Core Saturation Coefficient 3 1.30 to 5.00 1.30