5.7 H: Terminal Functions
184 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
■ H6-02: Pulse Train Input Scaling
The pulse train input scaling parameter sets the terminal RP input frequency that is equal to 100% of the signal selected
as the input value in parameter H6-01.
■
H6-03: Pulse Train Input Gain
Sets the level of the value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to terminal
RP.
■
H6-04: Pulse Train Input Bias
Sets the level of the value selected in H6-01 when a 0 Hz signal is input to terminal RP.
■
H6-05: Pulse Train Input Filter Time
Sets the pulse train input filter time constant in seconds.
The pulse train input filter time is useful for preventing noise interference from causing erroneous operation when
operating the drive with the pulse train signal. The longer the filter time is, the more effective the noise prevention is,
although this increasingly slows drive response time.
■
H6-06: Pulse Train Monitor Selection
Selects the pulse train monitor output terminal MP function. The set value is equal to the numerals in U- of
the selected monitor. Refer to U: Operation Status Monitors on page 358 for a complete list of monitors. Selectable
monitor items are listed below.
■
H6-07: Pulse Train Monitor Scaling
Pulse train monitor scaling sets the output frequency at terminal MP when the monitor item is 100%. Set H6-06 to 102
and H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.
■
H6-08: Pulse Train Input Minimum Frequency
Sets the minimum output frequency that can be detected by the pulse train input. Decreasing this setting reduces the time
the drive needs to react to changes in the input signal.
• If the pulse input frequency falls below this level, the pulse input value will be 0.
• Enabled when H6-01 = 0, 1, or 2.
• When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency
becomes the detection time for PG disconnect (F1-14).
No. Name Setting Range Default
H6-02 Pulse Train Input Scaling 100 to 32000 Hz 1440 Hz
No. Name Setting Range Default
H6-03 Pulse Train Input Gain 0.0 to 1000.0% 100.0%
No. Name Setting Range Default
H6-04 Pulse Train Input Bias -100.0 to 100.0% 0.0%
No. Name Setting Range Default
H6-05 Pulse Train Input Filter Time 0.00 to 2.00 s 0.10 s
No. Name Setting Range Default
H6-06 Pulse Train Monitor Selection
000, 031, 101, 102, 105,
116, 501, 502, 702 to 711,
801 to 809
102
No. Name Setting Range Default
H6-07 Pulse Train Monitor Scaling 0 to 32000 Hz 1440 Hz
No. Name Setting Range Default
H6-08 Pulse Train Input Minimum Frequency 0.1 to 1000.0 Hz 0.5 Hz