EasyManua.ls Logo

YASKAWA T1000V - Page 257

YASKAWA T1000V
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.5 Alarm Detection
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 257
Troubleshooting
6
LED Operator Display Minor Fault Name
CE
MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.
Cause Possible Solutions
Minor Fault
(H2- = 10)
A data error occurred due to noise.
Check options available to minimize the effects of noise.
Counteract noise in the control circuit wiring, main circuit lines and ground wiring.
Reduce noise on the controller side.
Use surge absorbers on magnetic contactors or other equipment causing the
disturbance.
Use cables recommended by Yaskawa or another type of shielded line. The shield
should be grounded on the controller side or on the drive input power side.
Separate all wiring for communications devices from drive input power lines. Install
an EMC noise filter to the input side of the drive input power.
YES
Communication protocol is
incompatible.
Check the H5 parameter settings as well as the protocol setting in the controller.
Ensure settings are compatible.
YES
The CE detection time (H5-09) is set
shorter than the time required for a
communication cycle to take place.
Check the PLC.
Change the software settings in the PLC.
Set a longer CE detection time (H5-09).
YES
Incompatible PLC software settings or
there is a hardware problem.
Check the PLC.
Remove the cause of the error on the controller side.
YES
Communications cable is disconnected
or damaged.
Check the connector for a signal through the cable.
Replace the communications cable.
YES
LED Operator Display Minor Fault Name
CrST
Can Not Reset
During a fault, the fault reset signal was entered while a Run command was activated.
Cause Possible Solutions
Minor Fault
Output
(H2- = 10)
A fault reset was being executed while
the Run command was still enabled.
Ensure that a Run command cannot be entered from the external terminals or option
card during fault reset.
Turn off the Run command.
YES
LED Operator Display Minor Fault Name
dEv
Speed Deviation (for Simple V/f with PG)
According to the pulse input (RP), the speed deviation is greater than the setting in F1-10 for a time
longer than the setting in F1-11.
Cause Possible Solutions
Minor Fault
Output
(H2- = 10)
Load is too heavy Reduce the load. YES
Acceleration and deceleration times are
set too short.
Increase the acceleration and deceleration times (C1-01 through C1-08). YES
The load is locked up. Check the machine. YES
Parameter settings are inappropriate. Check the settings of parameters F1-10 and F1-11. YES
The motor brake engaged. Ensure the brake releases properly. YES
LED Operator Display Minor Fault Name
EF
Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for over 0.5 s.
Cause Possible Solutions
Minor Fault
Output
(H2- = 10)
Sequence error
Check the forward and reverse command sequence and correct the problem.
Note: When minor fault EF detected, motor ramps to stop.
YES

Table of Contents

Related product manuals